Dontek AQUASMART 5 SV Gebrauchsanweisung - Seite 9

Blättern Sie online oder laden Sie pdf Gebrauchsanweisung für Controller Dontek AQUASMART 5 SV herunter. Dontek AQUASMART 5 SV 13 Seiten.

Anti-freeze function, when switched to ON will start the pump when the roof
temperature drops to the selected temperature.
FREEZE PROTECT?
It will operate for 3 minutes every 30 minutes until the roof temperature rises above
NO/YES
the selected temperature.
(RANGE 1.0°C-6.0°C)
Default setting is NO.
Anti-boil function.
If you select NO, the next option will be offered.
If you select YES, the pump will start when the roof temperature rises to the selected
BOIL PROTECT?
temperature. It will operate for the selected number of minutes, where the controller
NO/YES
will then take a roof temperature reading and either start the solar pump again (if roof
o
o
(Range 55
C - 99
C)
temp is still above selected temperature) or stop running the pump if the temperature
(Range 3 - 59mins)
has dropped below the selected temperature.
Default is NO. If you select Boil Protect to be YES, the controller will display 99
3mins. Adjust to required temperature and time.
For use when solar collectors are flooded, flat and may require a wetted roof sensor for
this mode.
The controller will allow the pool to heat to the selected pool temperature, where it will
then force the controller to stop any further solar heating of the system by not allowing
the solar pump to run once the roof temperature reads above the selected Pipe

PIPE PROTECTION?

Protection setting.
NO/YES
The solar pump will be allowed to run once the roof temp drops below the selected
o
o
Range 50
C - 95
C
Pipe Protection temperature.
Default is NO. If you select Pipe Protect to be YES, the controller will display 80
Adjust to required temperature.
Note – Pipe Protection will not be offered if Boil Protection has been turned ON.
CALIBRATE POOL
X.X (RANGE -5.0 TO +5.0°C)
SENSOR BY:
This is for the + series sensor only (TS02P).
1. If any of the menu items are left unattended for 3 minutes the menu will time
2. If a sensor fault is detected, the controller displays which sensor and what the
3. Should power be interrupted for any reason, the controller will resume normal
NOTES:
4. If the controller has stopped the pump and is displaying a higher temperature
5. MAX combined rated output load for the 240V socket(s) is 9.98 Amps / 2395
6. Degree of protection against moisture: IP33.
7. Store pool chemicals safely, at least 3 metres away from all pool equipment.
AQUASMART 5 SV v1.4
out and automatically save all settings and return to automatic operation.
fault is.
operation when power is restored. All information will have been kept for up to
10 days.
than expected it may be caused by a pump which is failing to prime. Check the
pump and if necessary, prime the pump as per the pump manufacturers'
instructions. Then reset the controller by turning it off/on.
Watts.
o
C for
o
C.
9