UP/DOWN button, press SELECT to accept. If
you select OFF then you will be prompted to
the anti-boil selection. If you selected ON
then you will be prompted to adjust the anti-
freeze start temperature point as follows;
"FREEZE° x "adjust with the UP/DOWN button,
press SELECT to accept. Once the roof
temperature gets to the anti-freeze setting or
below then the pump will be turned on for 3
minutes then turn off for 30 minutes, this
sequence
will
repeat
temperature rises above the anti-freeze
temperature.
The next item is anti-boil, you will be
prompted by BOIL? ON/OFF, adjust with the
UP/DOWN button, press SELECT to accept, if
you select OFF then the above settings will be
saved and the unit will restart. If you selected
ON then you will be prompted to adjust the
anti-boil start temperature point as follows;
"BOIL °xx" adjust with the UP/DOWN button,
press SELECT to accept. The unit will save the
new settings and restart. Once the roof
temperature gets to the anti-boil setting or
above then the pump will be turned on for 5
minutes then turn off for 15 minutes, this
sequence
will
repeat
temperature
drops
temperature. The customer is to be made
aware that these features have been turned
on and that the controller must remain
turned on at all times.
Aquasun 3 Instruction_rAD.docx
until
the
roof
until
the
roof
below
the
anti-boil
NOTES
1. If a sensor fault is detected the controller
will display which sensor failed (POOL
and/or ROOF) and the type of failure.
2. Should power be interrupted for any
reason, the controller will resume normal
operation when power is restored, all
information will have been kept for up to
14 days.
3. Temperature sensor used with this unit is
digital and is accurate to 0.5°C, no
calibration is required.
4. The sensor cable with the thin trace is the
positive and is usually fitted to the right
hand side of the green plug when looking
at the plug screws, incorrect polarity will
be displayed as a short circuit or reversed
fault.
5. If the controller has stopped pumping and
is displaying a higher temperature than
expected it may be caused by a pump
which is failing to prime, check the pump
and if necessary prime the pump as per
the pump manufacturers' instructions
then reset the controller by turning it
off/on.
6. Maximum rated output load for the 240V
socket is either, 10 Amps / 2400 Watts, or or or or,
15 Amps / 3600 Watts. Please refer to the
unit's rating label.
4