Installation and maintenance
6. According to the wall thickness, cut the suitable length of the flexible pipes, connect the
pipes to the OA inlet grille and EA outlet grille, please pay attention that the eave of the
cover is at the top
7. Input the pipes to the wall, seal the gap between wall and the pipes by sealant from
outdoor
8. Connect the another sides of the pipes to the flanges on side of the ventilator
9. After the installation is completed, power on the ventilator
OA and RA primary filter maintenance and change
OA primary filter is at the side of the ventilator while
RA primary filter is at the bottom of the ventilator, as
showed by the right picture, they are to filter the large
particle in the air
- Open the covers according to the marks on the ventilator,
take out the primary filters
- It is advised to clean the OA primary filters every 1-2
months
- It is advised to clean the RA primary filters every 3-4
months
HEPA filter change
HEPA filter is at the top of the ventilator, as showed by
the right picture, it is used to filter the small particle
that less than 2.5μm in the air
- Open the covers according to the marks on the ventilator,
take out the HEPA filters and change to be the
new one
- Recommended exchange period of the HEPA filter is
10 to 12 months