Akytec ITP11-G-W Handbuch

Blättern Sie online oder laden Sie pdf Handbuch für Messgeräte Akytec ITP11-G-W herunter. Akytec ITP11-G-W 2 Seiten.

Akytec ITP11-G-W Handbuch
Ordering code
Display colour:
R - red
G - green
Enclosure type:
W - universal mounting
Specifications
Supply current
Voltage drop
Input signal
Measuring range
Accuracy
Sampling rate (without damping)
Ambient temperature
Application class according to IEC 61140
IP Code
Dimensions (without carrier and cable gland)
Weight
Mounting
Cable clamping range
P
*
ower supply must be provided not only for ITP11, but also for a sensor. The device voltage drop of 10 V has to be taken into
NOTICE
account.
ITP11-W_0217_EN
© All rights reserved. Subject to technical changes and misprints.
Functions
The ITP11 is a universally applicable digital display unit. It is designed to be connected to any device
with a 4-20 mA output (current loop).
The device has the following functions:
Process value is displayed in accordance with the set limit values and the decimal point position
Display range -999...9999
Filter for damping the signal fluctuations with an adjustable time constant
Switching between linear and square root (for special transmitters)
Displaying error message when exceeding the measuring limit
Protection against unauthorized access
Fig. 1
Fig. 2
ITP11-W
Installation
1.
Remove the slide covers (1) in the direction of the arrows (Fig. 2).
2.
Unscrew the screws (3) and remove the front panel (2).
3.
Screw the cable glands (included) with the sealing rings (5) tightly into
the enclosure, so as to guarantee the IP65 protection.
4.
Not used cable entry has to be locked with the blind cap (included).
5.
Feed the cable through the cable gland into the enclosure.
6.
Connect the wire ends according to the wiring diagrams (Fig. 4 - 6)
and tighten the cap nut (6).
7.
Put the front panel (2) back and fasten it with the screws (3).
8.
To mount the device on DIN rail attach the carrier (7) to the device
using the two screws (4) and snap the device onto the DIN rail.
9.
To mount the device on a tube attach the carrier (7) to the tube using
two 6 mm wide cable ties (Fig. 3), then attach the device to the carrier
(7) using the screws (4).
10. To mount the device on the wall use the two holes for the screws (4)
11. Snap the two slide covers (1) onto the front panel (2).
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany
from current loop
≤ 10 V *
4-20 mA
3.8...22.5 mA
0.2% + 1 digit
1 reading / s
-40...+80 °C
III
IP65
70 x 50 x 28 mm
approx. 150 g
DIN rail, wall, tube
Ø 3...6 mm
Fig. 3
Tel.: +49 (0) 511 16 59 672-0 ·
www.akytec.de