□ Parameter Table
Address
Menu
30001
Firmware version
30002
YEAR
30003
MONTH
30004
DATE
30005
WEEKDAY
30006
HOURS
30007
MINUTES
30008
SECONDS
Alarm
30010
(SET : 1, RESET : 0)
30011
Measured value(temp.)
Measured value
30012
(humidity)
30013
Measured value( CO
)
2
30014
Sensor error
Setting
Address
Menu
40004
Language
40005
PASSWORD
40006
Button sound
40007
Alarm sound
40008
Comunication ID
40009
Communication parity
40010
Communication parity bit
40012
LCD light
Data
Description
INT16
-
INT16
Year
INT16
Month
INT16
Date
0 : Mon
1 : Tue
2 : Wed
INT16
3 : Thu
4 : Fri
5 : Sat
6 : Sun
INT16
Hour
INT16
Min.
INT16
Sec.
BIT0 : the lower temp. limit
BIT1 : the upper temp. limit
BIT2 : the lower humidity limit
INT16
BIT3 : the upper humidity limit
BIT4 : the lower CO
BIT5 : the upper CO
Display real-time
INT16
measurement temp.( x100 )
Display real-time
INT16
measurement humidity( x100 )
INT16
CO
2
0 : non error
1 : temp. or humidity error
INT16
2 : CO
error
2
3 : temp. or humidity or CO
Data
Description
0 : English
INT16
1 : Korean
INT16
Setting mode password
0 : OFF
INT16
1 : ON
0 : OFF
INT16
1 : ON
INT16
MODBUS ID
0 : 4800
1 : 9600
2 : 19200
INT16
3 : 38400
4 : 57600
5 : 115200
0 : NONE
INT16
1 : EVEN
2 : ODD
INT16
LCD setting( 1: ON, 0: OFF )
Unit
Step
-
0.1
-
1
-
-
-
1
-
1
-
1
-
1
-
1
-
1
limit
2
limit
2
℃
0.01
℉
%RH
0.01
PPM
1
-
1
error
2
Unit
Step
-
Toggle
-
1
-
Toggle
-
Toggle
-
1
BPS
1
-
1
-
Toggle
- 7 -
Min.
Max.
-
-
-
-
-
-
1
255
0
6
0
23
0
59
0
59
0
6
-10.00
60.00
14.00
140.00
0.00
100.00
0
9999
0
3
Min.
Max.
0
1
0
9999
0
1
0
1
1
32
0
5
0
2
0
1
Default
-
-
-
-
-
-
-
-
-
℃
-
Default
0
0
1
1
1
5
0
1
R20210514