Comax A105 Series Installationshandbuch - Seite 5

Blättern Sie online oder laden Sie pdf Installationshandbuch für Redner Comax A105 Series herunter. Comax A105 Series 12 Seiten.

INSTRUCTION & SERVICE MANUAL
A105
• All models are approved for use as Audible Signal Appliance
for use as General Signaling: UL464A & CSA C22.2 No 205-17
• Type 4 / 4X / 3R / 13, IP66
• -40°C to +66°C / -40°C to +151°F
General Signaling Canada:
A105.024.2: -40°C to +55°C / -40°F to +131°F
A105.230.7: -40°C to +40°C / -40°F to +104°F
• To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs
• EOL Monitoring (DC Only): End of Line Devices may be fitted between the +ve & -ve terminals of the PCBA. Please ensure that the device
legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short. Refer to the compatible
control panel specification for EOL device values and ratings.
Model
A105.024.2
A105.230.7
*Max Operating current for worst-case input voltage;
The units have been tested and approved to DNVGL-CG-0339 & EN54-3:2014
incl. A1:2019 for the installation on ships in the following locations:
Temperature:
A, B, C & D (Machinery spaces, control rooms,
accommodation, bridge, inside cubicles,
desks, etc..., pump rooms, holds, rooms with no
heating, Open deck, masts)
Humidity:
A & B (All locations)
Vibration:
A (Bulkheads, Beams, Deck, Bridge)
EMC:
A (All locations except Bridge & open deck)
Enclosure:
A, B & C, IP66 (Control rooms, accommodation,
bridge, engine room, open deck masts, below floor
plates in engine room)
Nominal Voltage
12V dc
24V dc
48V dc
48V ac
24 - 260V ac 50/60Hz /
115V ac
230V ac
#
Nominal current at nominal voltage and Tone 12
Voltage Range
Nominal Operating Current
10 - 60V ac
60-260V dc
The units comply with Solas 74 Chapter II-2, Regulation 7 & Chapter X,
Regulation 3 for installation on ships in the following locations:
Temperature:
Vibration:
EMC:
Enclosure:
#
Max Operating RMS*
17mA
33.5mA
113mA
42mA
25mA
17mA
D (Location -25° to +70°C)
A (General Applications)
A (General Power Distribution Zone)
IP66, Salt mist
125mA
42.5mA