WIRING LINKING BEACON & SOUNDER
A
FACTORY FITTED
Single Stage Configuration
Line Monitoring
Set to positive switching (default)
Stage 1: Apply Power to Stage 1 +ve & Stage 1 -ve
B
C
D
E
Stage 1 +ve IN
Stage 1 +ve OUT
Stage 1 -ve IN
Stage 1 -ve OUT
F
DRAWING TO BS8888:2000
DRAWN
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
J.SPILLER
ANGULAR DIMENSIONAL TOLS
CHECKED
G
B.ISARD
STANDARDS
APPROVED
SPECTRALARM RANGE
R.N.POTTS
3
4
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
RECOMMENDED MINIMUM VALUES:
14V MAX SYSTEM = 120Ω MIN, 2W MIN OR 1KΩ MIN, 0.5W MIN
28V MAX SYSTEM = 470Ω MIN, 2W MIN OR 2.4KΩ MIN, 0.5W MIN
Linked Sounder & Beacon Activation (Default)
Config.: 1a
Two Stage Configuration
Common Negative
Set to positive switching (default)
Stage 1: Apply Power to Stage 1 +ve & Common -ve
Stage 2: Apply Power to Stage 2 +ve & Common -ve
*Stage 2 only available for AB112S, AB112L or
AB121L beacons
+
-
Stage 1 +ve IN
+
Stage 1 +ve OUT
+
Common -ve IN
-
Common -ve OUT
-
Stage 2 +ve
SURFACE FINISH
WEIGHT (Kg)
DATE
28/06/2021
MATERIAL
DATE
28/06/2021
ALTERNATIVE MATERIAL
DATE
28/06/2021
5
6
Config.: 1b
S2*
-
+
+
-
+
+
-
-
S2
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
7
8
9
ISSUE
MOD No.
REASON - INITIAL - DATE
INTRODUCTION
A
JS- 28/06/2021
Three/Four Stage Configuration
Common Negative
Set to positive switching (default)
Stage 1: Apply Power to Stage 1 +ve & Common -ve
Stage 2: Apply Power to Stage 2 +ve & Common -ve
Stage 3: Apply Power to Stage 3 +ve & Common -ve
Stage 4: Apply Power to Stage 2 +ve, Stage 3 +ve & Common -ve
*Stage 2 only available for AB112S, AB112L or
AB121L beacons
**Stage 3 only available for AB121L beacon
Stage 1 +ve IN
Stage 1 +ve OUT
Common -ve IN
Common -ve OUT
Stage 2 +ve
Stage 3 +ve
ALL DIMENSIONS IN MM
IF IN DOUBT, ASK -
DO NOT SCALE
AB112/AB121 COMBINED SOUNDER
TITLE
& BEACON WIRING DIAGRAMS
SCALE
SHEET
DRAWING NUMBER
NTS 1
8
OF
10
A
Config.: 1c
B
C
S3**
S2*
-
D
+
+
-
E
+
+
-
-
F
S2
S3
A3
G
D118-06-501