Advanced Axis AX Series Handbuch für Installation und Betrieb - Seite 8
Blättern Sie online oder laden Sie pdf Handbuch für Installation und Betrieb für Kontrolleinheit Advanced Axis AX Series herunter. Advanced Axis AX Series 18 Seiten. Conventional zone module
2.2
DIP Switch Programming
Each AX-CZM module has four DIP switch settings for programming module functionalities. The AX-CZM module
can be setup as eight (8) Class B or four (4) Class A conventional zones, configured for local earth/ground fault
monitoring, if the host panel's power supply does not provide earth/ground fault detection capabilities, and can be
configured for either 3.9K, 4.7K or 6.8K Class B end-of-line (EOL) monitoring.
AX-CZM Module Default Dip Switch Settings = All OFF:
Segment 7 OFF:
Earth/ground fault monitoring is performed by host panel's power supply. If AX-CZM local
earth/ground fault monitoring is required, slide DIP switch segment 7 to the ON position.
Note: If multiple AX-CZM modules require earth/ground fault monitoring and they are receiving power from
a common power supply source only one (1) of the AX-CZM modules should be set to AX-CZM local
earth/ground fault monitoring.
monitoring the earth/ground fault reference impedance is 75K.
Segment 6 OFF:
Class B wiring for all conventional zones. If Class A wiring is required, slide DIP switch
segment 6 to the ON position.
Segment 3 – 5 OFF:
Unused dip switch segments, position has no relevance, leave in the OFF position.
Segment 1 – 2 OFF:
Class B end-of-line (EOL) value 6.8K. If a 4.7K or 3.9K Class B end-of-line is required, set
DIP switch 1 and 2 as indicated below:
8
In addition, if an AX-CZM module is performing earth/ground fault
DIP 1
DIP 2
0 (OFF)
0 (OFF)
6.8K (Default)
1 (ON)
0 (OFF)
4.7K
0 (OFF)
1 (ON)
3.9K
1 (ON)
1 (ON)
Unused (6.8K)
Setting
www.advancedco.com