8. Input and output relationship
OUTPUT
[V][mA]
5 1
0 0
-5 -1
5
0
1
0
Power
Power
transmission
receiving
9. Calibration
Because this product is adjusted, there is not need of calibration especially.
However, if discrepancy arises in an output in long-term use, please adjust in the next way.
Remove the terminal cover and VR cap before adjustment, and attach the VR cap and terminal cover after adjustment.
(1) For the output load, connect an actual load (within the output load range indicated on the name plate)
or a simulated load with the same resistance value as the actual load.
(2) Apply the auxiliary power supply (rated) and the input equivalent to 50% of the rated output value, and
energize for 15 minutes.
(3) Enter the lower limit of the rated output range and adjust with BIAS adjustment VR so that the output becomes
the lower limit.
Next, enter the upper limit of the rated output range and adjust the MAX adjustment VR so that the output
reaches the upper limit.
(The screwdriver for adjustment:Tip width of 1.8 to 2.3mm, Phillips-head screwdriver or flat-blade
screwdriver)
OUTPUT
[V][mA]
5 20
3 12
1
4
5
5 [A]
INPUT
1
1 [A]
Power
transmission
OUTPUT
[V] [mA]
5
2.5 0.5
0
0
5 [A]
INPUT
0
1 [A]
Power
receiving
12
1
0
5
0
5 [A]
1
0
1 [A]
Power
Power
transmission
receiving
Q-222-030
INPUT