Daiichi Electronics HSQT2-93A Gebrauchsanweisung - Seite 6

Blättern Sie online oder laden Sie pdf Gebrauchsanweisung für Messwertaufnehmer Daiichi Electronics HSQT2-93A herunter. Daiichi Electronics HSQT2-93A 16 Seiten. High speed multi power line transducer

2.2 Measurement parameter

Measurement
parameter
Rating 5A
Current
[ A ]
Rating 1A
Voltage
[ V ]
Rating 5A
Active power
[ W ]
Rating 1A
Rating 5A
Reactive
power
[ var ]
Rating 1A
(1) 45~55Hz
Frequency
(2) 55~65Hz
[ Hz ]
(3) 45~65Hz
About measurement
(1) A class index is a rated-frequency 50/60Hz ±10% value. Linearity is within ±0.3%.
(2) In ±10% of rated frequencies, current, voltage, power, and reactive power are normally measured, in case
the voltage between input lines is 10V or more. If the voltage between input lines is 60V or more, it is
measurable to the frequency of 168Hz. (However, outside of an accuracy guarantee)
(3) In case the voltage between input lines is 30V or more, frequency is measured normally.
Note(
) The critical value of measuring range constitutes the following.
Current:0~120% of measuring range
Voltage:0~156V(3-phase 3-wire),0~156/√ 3V(3-phase 4-wire)
[Measures to +30% at the 120V(120/√ 3V) cases of rating]
Active power (One-side swing):-20~+120% of measuring range,
Active power (Both swing),Reactive power:-120~+120% of measuring range.
Note(
) In case current, power, and reactive power measure the next inverter output directly, an error becomes
large. Cycle control, SCR phase angle control, PWM control.
Note(
) S phase current of 3-phase 3-wire is for 2CT input, calculates in R phase and T phase current combination.
And, TR line voltage is for 2VT input, calculates in RS and ST line voltage combination.
Measuring range (
)
0~5A
0~1A
0~150V
(3φ3W)
0~150/√ 3V (3φ4W)
(1) 0~1000W
(2) 0~833.3W
(3) 0~750W
(4) 0~500W
(5) -1000~+1000W
(6) -833.3~+833.3W
(7) -750~+750W
(8) -500~+500W
(1) 0~200W
(2) 0~166.7W
(3) 0~150W
(4) 0~100W
(5) -200~+200W
(6) -166.7~+166.7W
(7) -150~+150W
(8) -100~+100W
(1) LEAD 1000~LAG 1000var
(2) LEAD 833.3~LAG 833.3var
(3) LEAD 750~ LAG 750var
(4) LEAD 500~ LAG 500var
(1) LEAD 200~LAG 200var
(2) LEAD 166.7~LAG 166.7var
(3) LEAD 150~ LAG 150var
(4) LEAD 100~ LAG 100var
Class
Operation method
index
0.5
Effective-value
(
)
arithmetic
Fundamental-wave
0.5
effective-value
(
)
arithmetic
0.5
Time division
(
)
multiplication
0.5
Time division
(
)
multiplication
0.5
Zero cross cycle
(
)
arithmetic
5
Q-208-081
Note
Average value of each phase
current (R, S, T)
(
)
3φ3W:Average value of each
line voltage
(RS,ST,TR)
(
3φ4W:The average value of
each phase voltage
(RN,SN,TN)
It can alter into the
measuring range of (1)~(8)
with front DIP switch.
It can alter into the
measuring range of (1)~(4)
with front DIP switch.
Voltage V(RS) or V(RN) is
measured.
It can alter into the
measuring range of (1)~(3)
with front DIP switch.
)