Programming of the device
Selection of the threshold of switch-on and switch-off ventilation
It is possible to program the threshold for enabling and disabling the ventilation.
• Selection the threshold for disabling ventilation
The FAN LED is on, with fixed light indicates this phase of programming.
With ← and → keys select the value of temperature indicated on display.
Interval of programming: from -25°C up to (enabling threshold -1°C)
Confirm with ENTER.
• Selection the threshold for enabling ventilation
The FAN LED is on, with flashing light indicates this phase of programming.
With ← and → keys select the value of temperature indicated on display.
Interval of programming: from (disabling threshold +1°C) up to 200°C
Confirm with ENTER.
Selection of the alarm and trip threshold
The FAN This setting starts to program from the channel number 1.
The ALARM LED ON indicates the programming of the alarm:
With ← and → keys select the value of temperature
Interval of programming: from -25°C up to (trip threshold -1°C)
Confirm with ENTER.
The TRIP LED ON indicates the programming phase of the tripping threshold.
With ← and → keys select the value of temperature
Interval of programming: from (alarm threshold +1°C) up to 200°C.
Confirm with ENTER.
Repeat the same operation for the successive channels.
Selection of address network identification for the communication of the serial
port (MODBUS-RTU protocol)
This setting is significant only for eDTI model.
This setting is indicated on displays with:
• value to set on T1-T2 display
• ID on T3-T4 display.
With ← and → keys select the number choice
The range for accepted value is from 1 to 247.
Confirm with ENTER.
Modbus setting
Setting address MODBUS network
10
NOTE
TEMPERATURE MONITORING UNIT DTI AND EDTI
T1-T2 display
001
T3-T4 display
ID