(2) Be sure to insert Drain hose 1 to the very end of the Drain pan of the unit with no
space.
Ensure there
is no space.
5 to 10 mm
1 Drain hose
Drain pan
Fasten the Hose band 2 at the position where
horizontal against earth (ground).
The Hose band 2 must be positioned at the right
side of the Drain hose 1 as in the fi gure.
Do not connect to the Drain hole with adhesive. Using adhesive may cause damage
and water leaks.
(3) After installing the Drain hose 1 , check if the drainage is smooth.
Good
To prevent excessive force on Drain hose 1 , avoid bends or twists. (To bend or twist
may cause water leaks.)
(4) After checking for drainage, attach the Drain hose insulation B 3 to insulate, following
the instructions as in the figures.
To avoid space with Drain hose 1 and Hose band 2 , press firmly the Drain hose
insulation B 3 .
Ensure there is
no space.
En-9
Applying
area of
Joint pipe
adhesive
(Field supply)
Drain pipe (VP25)
(Field supply)
4 mm or less
2 Hose band
CAUTION
Downward
gradient
2.5 to 5.0 mm
Prohibited
CAUTION
3 Drain hose insulation B
(Accessories)
Butt the insulation
against the unit.
STEP 1
STEP 2
Press
firmly.
Roll the insulation
over the joint.
STEP 3
• When using the drain port on the left side of the unit, remove the drain cap and install it to
the right side drain port.
Unit
Make sure the drain water is properly drained.

6. ELECTRICAL WIRING

Electrical work must be performed in accordance with this Manual by a person certifi ed
under the national or regional regulations. Be sure to use a dedicated circuit for the
unit.
An insuffi cient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or fi re.
Before starting work, check that power is not being supplied to the all units.
For wiring, use the prescribed type of cables, connect them securely, making sure that
there are no external forces of the cables applied to the terminal connections.
Improperly connected or secured cables can cause serious accidents such as
overheating the terminals, electric shock, or fi re.
Securely install the electrical box cover on the unit.
An improperly installed electrical box cover can cause serious accidents such as
electric shock or fi re through exposure to dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit
could result.
Control box
Slit
Press firmly.
Slit
Press
firmly.
FINISH