Setting
Setting range
Remote control-
0 to 15
ler address
Example
If 4 indoor units are connected.
Indoor unit
Indoor unit
RC AD SW
RC AD SW
0
1
Remote
controller
RC AD SW
0
1
Address
0
1
RC AD SW
8
9
Address
8
9
ii) 2-wire type
Rotary switch (RC AD SW)...Factory setting "0"
Since the remote controller address settings are automatically confi gured, you do not
need to confi gure them.
If confi guring manually, it is necessary to confi gure both the indoor unit and the
remote controller. For details, please refer to the remote controller manual.
] 1
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up. (Fig. B)
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Fig. B
Confusion
Indoor unit
Remote
controller
• Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, 2, referring to the Table B.
ON
OFF
SW
SW
1
A (Factory setting)
DIP switch SET 3
OFF
SW1
DIP switch SET 3
OFF
SW2
Type of switch
Setting
example
0
RC AD
Indoor unit
Indoor unit
RC AD SW
RC AD SW
2
3
2
3
4
5
6
2
3
4
5
6
A
B
C
D
E
10
11
12
13
14
Code change
A
B
C
D
A
B
C
D
DIP switch "SET3"
SW
SW
2
3
4
Table B
Custom code
B
C
ON
OFF
OFF
ON
7.3. Switching the upper limit of cooling
temperature
This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
• Wired remote controller (2-wire type)
• Central remote controller
• Touch panel controller
• System controller
• Service tool
• Web monitoring tool
DIP switch setting
Set the DIP switch SET 4 SW3 referring to the Table C.
7
7
F
15
Table C
DIP switch SET 4 SW3
OFF (Factory setting)
ON
NOTE:
Please do not make a standard setup and an extension setup intermingled in remote
controller group.
] 1
7.4. Function setting
Please make this setting after completing all construction works.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
Setting number
number
00
Filter
indicator
11
01
interval
02
00
D
01
Filter indi-
ON
13
cator action
ON
02
00
Horizontal
swing
24
01
airfl ow
direction
02
00
Cool air
tempera-
30
01 Adjust (1)
ture trigger
02 Adjust (2)
ON
DIP switch "SET4"
OFF
SW
SW
SW
SW
1
2
3
4
Cooling temperature setting range
Standard (18 to 30 °C)
Extension (18 to 32 °C)
WARNING
Default
○
Default
Adjust the fi lter cleaning interval noti-
fi cation. If the notifi cation is too early,
Longer
change to setting 01. If the notifi cation
is too late, change to setting 02.
Shorter
○
Enable
Disable
Enable or disable the fi lter indicator.
Display
Setting 02 is for use with a central
only on
remote controller.
central
remote
controller
○
Default
Adjust the horizontal swing airfl ow
direction.
Left half
(For horizontal swing equipped mod-
els)
Right half
○
Default
Adjust the cool air trigger tempera-
ture. To lower the trigger temperature,
use setting 01. To raise the trigger
temperature, use setting 02.
Details
En-12