AirStage AUXD24GALH Installationshandbuch - Seite 14

Blättern Sie online oder laden Sie pdf Installationshandbuch für Klimagerät AirStage AUXD24GALH herunter. AirStage AUXD24GALH 17 Seiten. Indoor unit (cassette type)
Auch für AirStage AUXD24GALH: Betriebshandbuch (6 seiten)

AirStage AUXD24GALH Installationshandbuch
Table A
Rotary Switch
Address
Setting
REF AD SW
Refrigerant
circuit
× 10
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
1
11
1
12
1
.
.
.
.
.
.
99
9
Do not set the indoor unit address (IU AD SW) at 64 to 99.
It may result in failure.
(3) Remote controller address
i) 3-wire type
Rotary switch (RC AD SW)...Factory setting "0"
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from 0.
Setting
Setting range
Remote controller
0 to 15
address
Example
If 4 indoor units are connected.
Indoor unit
Indoor unit
RC AD SW
RC AD SW
0
1
Remote
controller
RC AD SW
0
1
Address
0
1
RC AD SW
8
9
Address
8
9
ii) 2-wire type
Rotary switch (RC AD SW)...Factory setting "0"
Since the remote controller address settings are automatically confi gured, you do not
need to confi gure them.
If confi guring manually, it is necessary to confi gure both the indoor unit and the remote
controller. For details, please refer to the remote controller manual.

7.2. Custom code setting

Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Confusion
Indoor
unit
Remote
controller
En-13
Address
Rotary Switch Setting
IU AD SW
Indoor unit
× 1
× 10
0
0
0
1
1
0
2
2
0
3
3
0
4
4
0
5
5
0
6
6
0
7
7
0
8
8
0
9
9
0
0
10
1
1
11
1
2
12
1
.
.
.
.
.
.
.
.
.
9
63
6
Type of switch
Setting
example
0
RC AD
Indoor unit
Indoor unit
RC AD SW
RC AD SW
2
3
2
3
4
5
6
2
3
4
5
6
A
B
C
D
E
10
11
12
13
14
Code change
A
B
C
A
B
C
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2, referring to the Table B.
× 1
0
1
2
3
4
5
6
7
8
9
0
1
2
.
.
.
Table B
3
DIP switch SET 3 SW1
DIP switch SET 3 SW2

7.3. Switching the upper limit of cooling temperature

This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
• Wired remote controller (2-wire type)
• Central remote controller
• Touch panel controller
• System controller
• Service tool
• Web monitoring tool
DIP switch setting
Set the DIP switch SET 4 SW3 referring to the Table C.
7
7
F
15
Table C
DIP switch SET 4 SW3
OFF (Factory setting)
NOTE:
Please do not make a standard setup and an extension setup intermingled in remote
controller group.
D
D
ON
DIP switch "SET 3"
OFF
SW
SW
SW
SW
1
2
3
4
Custom code
A (Factory setting)
OFF
OFF
ON
OFF
SW
SW
SW
SW
1
2
3
4
Cooling temperature setting range
ON
Extension (18 to 32 °C)
B
C
D
ON
OFF
ON
OFF
ON
ON
DIP switch
"SET4"
Standard (18 to 30 °C)