AirStage AUXK024GLAH Installationshandbuch - Seite 11

Blättern Sie online oder laden Sie pdf Installationshandbuch für Klimagerät AirStage AUXK024GLAH herunter. AirStage AUXK024GLAH 13 Seiten. Indoor unit (cassette type)

Operation behavior
Connector
External output 1
Pins 1-2
External output 2
CNB01
Pins 1-3
External output 3
Pins 1-4

6.5.3 Connection methods

Wire modification
(1) Remove insulation from wire attached to wire kit connector.
(2) Remove insulation from field supplied cable. Use crimp type insulated butt connector
to join field cable and wire kit wire.
(3) Connect the wire with connecting wire with solder.
IMPORTANT:
Be sure to insulate the connection between the wires.
Locally purchased
Solder and insulate the connected parts.
Connection terminals and wiring arrangement
In following figure, all the possible connectors are connected for description.
In actual installation, you cannot connect all the connectors at once.
Cable hooks
CNB01
CNA01
CNA03
CNA02
CNA04
Cable clamp

7. FIELD SETTING

There are 3 methods for address setting by FIELD SETTING as follows.
Please set by either of the methods.
Each setting method is described in below (1) to (3).
(1) IU AD, REF AD SW settings: This section (7.1. Setting the address)
(2) Remote controller settings:
Refer to the wired or wireless remote controller manual
for detailed setting information. (Set IU AD, REF AD
SW to 0)
(3) Automatic address settings: Refer to the outdoor unit manual for detailed setting
information. (Set IU AD, REF AD SW to 0)

7.1. Setting the address

Use an insulated screwdriver to set the dip switches.
• Open the cover referring to the figure below. Close and fix the cover after addressing
setting.
(1) Loosen the screw.
(2) Slide the cover and open it.
Output voltage
Status
0V
Stop
DC 12 V
Operation
0V
Normal
DC 12 V
Error
0V
Indoor unit fan stop
DC 12 V
Indoor unit fan operation
Option parts:
External input /output wire
CAUTION
For refrigerant
For indoor
unit address
circuit address
IU AD
REF AD
×10
×1
×10
×1
SET3
SET4
7.1.1 Indoor unit address
• Rotary switch (IU AD × 1)...Factory setting "0"
• Rotary switch (IU AD × 10)...Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD
SW as shown in the Table A.
7.1.2 Refrigerant circuit address
• Rotary switch (IU AD × 1)...Factory setting "0"
• Rotary switch (IU AD × 10)...Factory setting "0"
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A for
each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
Setting
Indoor unit address
Refrigerant circuit
address
• If working in an environment where the wireless remote controller can be used, the ad-
dresses can also be set using the remote controller.
• If setting the addresses using the wireless remote controller, set the indoor unit address
and refrigerant circuit address to "00".
(For information on setting using the wireless remote controller.)
Table A
Address
Rotary switch setting
Refrigerant
circuit
× 10
0
1
2
3
4
5
6
7
8
9
10
11
12
.
.
.
99
Do not set the indoor unit address (IU AD SW) at 64 to 99.
It may result in failure.

7.2. Custom code setting

• Selecting the custom code prevents the indoor unit mix-up. (figure below)
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Indoor unit
Remote
controller
• Custom code setting for indoor unit
Set the DIP switch SET3 SW1, 2, referring to the
figure and table below.
RC AD
DIP switch "SET3"
ON
OFF
SW
SW
SW
1
2
Setting range
Type of switch
Setting
0 to 63
example 2
IU AD × 10
Setting ex-
0 to 99
ample 63
REF AD × 10
Address
REF AD SW
Indoor unit
× 1
0
0
0
0
1
1
0
2
2
0
3
3
0
4
4
0
5
5
0
6
6
0
7
7
0
8
8
0
9
9
1
0
10
1
1
11
1
2
12
.
.
.
.
.
.
.
.
.
9
9
63
Confusion
Code change
A
A
IU AD
×10
SET3
DIP switch "SET3"
DIP switch
A (Factory
SET3
setting)
SW1
OFF
SW2
OFF
SW
3
4
IU AD × 1
REF AD × 1
Rotary switch setting
IU AD SW
× 10
× 1
0
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
1
0
1
1
1
2
.
.
.
.
.
.
6
3
B
C
D
B
C
D
REF AD
RC AD
×1
×10
×1
SET4
Custom code
B
C
D
ON
OFF
ON
OFF
ON
ON
En-10