AirStage UTY-DTGGZ1 Installationshandbuch - Seite 5
Blättern Sie online oder laden Sie pdf Installationshandbuch für Controller AirStage UTY-DTGGZ1 herunter. AirStage UTY-DTGGZ1 9 Seiten. Touch panel controller
5. 3.
External input function
(1)
External input terminals
Function which uses external input terminals to perform the
"Emergency stop" or "Batch start/batch stop" operation from the
outside.
(2)
External input contact
CH1 and CH2 of TM201 of the rear cover are switched to "dry
contact terminal" and "apply voltage terminal" by connecting
CN201 on the front cover PCB to CN411 or CN412.
TM201- CH1, CH2
Dry contact terminal
Apply voltage terminal
*
:Factory setting
▪
Dry contact terminal
When a power supply is unnecessary at the input device you
want to connect, connect CN201 and CN411.
Connection example 1:
When the switch is connected
PCB
TM201
*1
*3.
Short circuit detection resistance (R ON) : ≤ 500 (Ω).
Open circuit detection resistance (R OFF) : ≥ 100 (kΩ).
*
A twisted pair cable 0.33mm
mum length of cable is 25m (82 ft).
Connection example 2:
When the electricity meter is connected
PCB
TM201
*
Connect the electricity meter to CH1. In this case, the use of
CH2 is prohibited.
▪
Apply voltage terminal
When a power supply must be provided at the input device,
connect CN201 and CN412.
CN411
CN412
Connect with the CN201
CN411 *
CN412
PCB
2
(22AWG) should be used. Maxi-
PCB
Connection example 1:
When the switch is connected
*2
PCB
DC power
supply 12-24V
*4
*3
*4
Connection example 2:
When the electricity meter is connected
*2
PCB
DC power
supply 12-24V
*3
*4.
Make the power supply DC12 to 24V. Select a power supply
capacity with an ample surplus for the connected load.
*5.
Do not impress a voltage exceeding 24V across K1-K2.
*6.
The allowable current is DC10mA or less. (Recommended
DC5mA)
Provide a load resistance such that the current becomes
DC10mA or less.
Select very low current use contacts (usable at DC12V,
DC1mA or less).
A twisted pair cable 0.33mm
mum length of cable is 25m (82 ft).
(3)
Selecting the function
The function of the external input terminals is disabled at the fac-
tory.
Select the function to be used (following table) by installer set-
ting of application.
*
Turn on the power and select by installer setting after starting
the application.
Emergency stop
Batch start/stop
Electricity meter
(4)
Input signal type
Emergency stop or batch
start
Edge
Emergency stop reset or
batch stop
Emergency stop or batch
start
Emergency stop reset or
Pulse
batch stop
Electricity meter signal
H: Energized state
L: Shutoff state
When Edge was selected, only CH1 can be used. CH2 cannot be
used.
PCB
TM201
PCB
TM201
2
(22AWG) should be used. Maxi-
Edge
Pulse
H
300 ms
CH1
or more
L
H
300 ms
CH1
L
or more
H
300 ms
CH1
or more
L
H
300 ms
CH2
or more
L
H
50 ms
CH1
or more
L
En-4