CommScope 760230946 Anleitungsblatt - Seite 6
Blättern Sie online oder laden Sie pdf Anleitungsblatt für Kabel und Anschlüsse CommScope 760230946 herunter. CommScope 760230946 9 Seiten. Powered fiber cable transition box

860660202
Rev. B
Instruction Sheet
Step 2 – Route and terminate outgoing/outdoor Powered Fiber Cable (PFC)
1. Route the outgoing PFC into the TB and secure to the strain relief bar with a supplied cable
tie, as shown in Figure 9. Ensure adequate length for fiber slack (1-1.5 meters).
2. Separate the cable into three sections along the tear lines, as shown in Figure 9.
3. For the outgoing power termination repeat steps 3 – 5 from Section 6 Step 1, verifying any
end device powered equipment wiring polarity with polarity connections on terminal strip,
as shown in Figure 10.
Note:
Polarization indentation along one side of the cable for polarity identification
Figure 8
© 2021 CommScope, Inc. All Rights Reserved
www.commscope.com