CommScope AMP NETCONNECT 2U Multi-Fiber Push-On Anleitungsblatt - Seite 3

Blättern Sie online oder laden Sie pdf Anleitungsblatt für Gehege CommScope AMP NETCONNECT 2U Multi-Fiber Push-On herunter. CommScope AMP NETCONNECT 2U Multi-Fiber Push-On 4 Seiten. Mpo secure rack-mounted enclosure assembly

Sliding Chassis onto Rear Brackets
Back of
Legs of
Chassis
Rear Brackets
Figure 4
Detail A — Front Brackets Secured to Rack (Ref)
Detail B — Back Brackets Secured to Rack (Ref)
Figure 5
4.4. Connect MPO Truck Cable Assemblies
Understand and follow the safety precautions given in
Section 3, then proceed with the following.
1. Label the end of each truck cable assembly.
2. Insert each truck cable assembly into the back of
the chassis so that it enters the applicable channel,
then slide the truck cable assembly through the
channel until the MPO connector exits the front of
the chassis. Allow a small amount of slack in the
truck cable assembly at the back of the chassis.
See Figure 6.
Rev B
Rails of Rack
(Ref)
Back of
Chassis
3. If desired, loosely wrap Hook and Loop Cable Tie
1375253-2, or similar cable tie, around the trunk
cable assemblies to provide strain relief at the back
of the rack or cabinet. Refer to Figure 6.
4. Connect the MPO connectors of each trunk cable
assembly to the back of an adapter of an MPO
adapter plate. Make sure to observe the port
designations marked on the front of the MPO
adapter plates. See Figure 7.
4.5. Install Adapter Plate(s)
Understand and follow the safety precautions given in
Section 3, then proceed with the following.
1. Using the captive screw attached to the MPO
adapter plate, install an MPO adapter plate onto the
front of the chassis for each opening to be used.
DO NOT remove the dust cap plugs. See Figure 7.
2. Using the captive screw attached to the blank
adapter plate, install a blank adapter plate or cable
management adapter plate assembly (includes 2
cable management saddles) onto the front of the
chassis for each opening without an MPO adapter
plate.
4.6. Connect Hydra Cable Assemblies
Understand and follow the safety precautions given in
Section 3, then proceed with the following.
1. Install Parking Cap 1553641-1 to any empty switch
blades that do not have a transceiver to support the
LC connector leg of the hydra cable assembly.
2. Connect the LC connectors of the hydra cable
assemblies to the applicable ports of the switch
blade (each LC connector is labeled to match the
port markings). See Figure 8.
Routing MPO Trunk Cable Assemblies
Trunk Cable Assembly
Entering Applicable Channel
Cable Tie
(Ref)
Figure 6
408-32067
Slack in Trunk
Cable Assembly
3 of 4