AIRTAK SD-10 Betriebsanleitung - Seite 2
Blättern Sie online oder laden Sie pdf Betriebsanleitung für Luftentfeuchter AIRTAK SD-10 herunter. AIRTAK SD-10 9 Seiten. Refrigerated air dryers
SPECIFICATIONS:
Refrigerant:
Maximum Inlet Pressure:
Maximum Inlet Temperature:
Minimum Ambient Temperature:
Maximum Ambient Temperature
OPERATION:
Under normal conditions, the air dryer will run continuously when power is on. The
dryer will provide a specified pressure dew point for the compressed air system with
little maintenance or adjustments required.
Moisture and condensation will be removed from the moisture separator automatically
through the automatic drain.
Units are designed for inlet air temperature of 100°F. If the inlet air temperature
exceeds 100°F, there is a possibility of overloading the refrigerant compressor.
The allowable range for ambient temperature is 50°F to 110°F. At ambient temperature
above 100°F, refrigeration capacity will decrease with a corresponding increase in
pressure dew point. If the thermal overload switch trips out and stops the compressor,
the unit will not restart until it has cooled.
INSTALLATION:
General:
A. Only qualified service people should install a compressed air dryer. Compressed
air, machinery and electricity are involved in installation; all can be dangerous if not
handled properly.
B. Upon unpacking your dryer, examine it for any external damage. If such damage
exists, report it to the delivering carrier immediately and file a freight claim with the
responsible carrier.
C. Prior to attempting installation of the dryer read the accompanying literature
thoroughly. Failure to follow the enclosed recommendations may result in invalidation
of the warranty.
D. Dryers are designed for installation and operation in typical indoor industrial
atmospheres. Do not install or operate dryers in hazardous locations or in explosive or
flammable atmospheres.
R134a
250 psig
120°F
50°F
110°F
2