6B. Option 2: The damper may also be installed in a steel stud/gypsum or masonry
partition, in a vertical or horizontal (retaining plate on top) position (blade running
horiztontal), with a retaining plate on one side of the partition. Installation: with the
factory installed retaining plate flush to the fire partition, place eight screws (#10
sheet metal for steel studs long enough to penetrate the metal stud by 1/2" minimum
or #10 by 1-1/4" masonry screws) equidistant around the perimeter of the retaining
plate. Screws are placed in each corner and halfway between the corners as shown.
7.
Electrical and/or pneumatic connections to damper actuators should be made in
accordance with wiring and piping diagrams developed in compliance with applicable
codes, ordinances, and regulations.
8.
Refer to the installation instruction for Drywall Type Construction for the material and
opening framing details.
9.
As with all joints, the contractor must seal duct-collar connections, in the field, after
installation.
OPTION 2: ANGLE 1 SIDE
8
5
6B
Typical wood, metal stud, or masonry opening.
(Refer to metal or wood stud framing for
fire dampers in drywall partitions.)
6B
1" Min. Typ.
(25mm)
OPTION 2
Auxiliary
Operating
Jackshaft
4
5
Cross section of opening.
All moving parts of the damper must be inspected and cycled at intervals not greater than every 12 months or in accordance with the
latest edition of NFPA 90A, 92A, local codes, and the actuator manufacturer. In addition, fuse links shall be removed and inspected for
corrosion. Dry lubricants are recommended.
This installation sheet has been reviewed and accepted by Underwriters Laboratories.
FORM 40003, page 2
4
1
3
Blade
Shaft
Manufacturer's Recommendations
When UL is referred to in this document, it represents UL/ULC.
OPTION 2
STEEL STUD OR MASONRY
WALL UL DESIGN
Fastener
Retaining
Plate
Clip Angle
Fastener
Wall Detail
1-1/2"
(38mm)
Same length as
cut in damper/
retaining plates
Splice Clip Detail
OPTION 2
Retaining Plate Detail
Damper
Sleeve
1-1/2"
(38mm)
1-1/2"(38mm)
1-1/2"
(38mm)
Clip Angle Detail
20 Ga. (1) Galv. Steel
Cutline on
Retaining
Plate
(Cover with
Splice Clip)