Anderson Thermal Solutions – FFA12 Burner Operation Manual
fuel and atomizing air metal hoses to the burner, making sure the connections
are correct.
Open the atomizing air (adjust it to about 2 bar), slowly open the fuel shutoff
valve at burner downcomer until the fuel begins to flow, and adjust the oil flow
control valve to obtain the required oil flow.
Note:
For the most suitable atomization of heavy oil, it needs to be preheated to make
its viscosity reach 100 SSU or lower. If the viscosity of the oil is increased (or the
temperature of the oil is lowered), the atomization effect will be worsened, the
efficiency of the burner will be reduced, and at the same time, the nozzle may
be clogged and carbon deposits.
After the burner is running, always check the flame angle and the connection of
the burner.
Adjust the cooling air pressure of the burner located on the non-combustion side
to about 0.3-0.5 bar
Stop
Before stopping the heavy oil pipeline system, it is necessary to flush the system
with diesel several times (or slightly adjust the time according to the specific
situation). After the burner purge is complete, stop and pull the oil burner.