Compact Electric CDMR-51 Handbuch - Seite 15
Blättern Sie online oder laden Sie pdf Handbuch für Relais Compact Electric CDMR-51 herunter. Compact Electric CDMR-51 15 Seiten. Digital line monitoring relay
Line Monitoring Relay CDMR-51
Param
Funct.
Parameter
No. *)
Setting Value
43
f<
47
f<
Return Delay
48
f<
44
f<
Output Relay
42
f<
Setting Value
36
f>
40
f>
Return Delay
41
f>
37
f>
Output Relay
35
f>
Setting Value
29
f>>
33
f>>
Return Delay
34
f>>
30
f>>
Output Relay
28
f>>
PS >
Setting Value
57
PS >
58
PS >
Blocking Time
61
PS >
62
PS >
Output Relay
56
Ba >
Setting Value
71, 73
Ba >
75
Ba >
Return Delay
76
Ba >
72, 74
Ba >
Output Relay
70
SEQ
Output Relay
77
General
79
:
Negated Relays
78
64
Lock-out Time
63
Lock out Relays
65
U> 10 Min. Mean v.
66
KU-Detection
67
fU Connect-Logic
80
Ext. Blocking
82
Self-Monitor. ->K5
98
Security Code
81
LCD Contrast
87
Language Setting
91-97
No user access, see chapter self-monitoring
*)
Note: Two numbers in this field refer to star and delta voltage.
CDMR51e_man_A11.doc
/ User Manual
Setting
Range
[45 -65] Hz
Trip Delay
[0,06 - 60] s
[0,06 - 60] s
Hysteresis
[0,00 – 5,00] Hz
K1 ..K5
[45 -65] Hz
Trip Delay
[0,06 - 60] s
[0,06 - 60] s
Hysteresis
[0 – 5,00] Hz
K1 ..K5
[45 -65] Hz
Trip Delay
[0,06 - 60] s
[0,06 - 60] s
Hysteresis
[0 – 5,00] Hz
K1 ..K5
[1- 30] °
Sensitivity
[0 - 1]
[1 - 20] s
Pulswidth
[1 - 20] s
K1 ..K5
[1 - 50%] Un
Trip Delay
[0,04 - 60] s
[0,04 - 60] s
Hysteresis
[0 - 20%] Un
K1 ..K5
K1 ..K5
Mains
3- /4-Wire
K1 ..K5
0 – 990 s
K1 ... K5
on / off [0/1]
on / off [0/1]
on / off [0/1]
0, 1, 2
on / off [0/1]
[ 0 - 999 ]
[ 0-20 ]
germ/engl [0/1]
Factory
Factory
Setting
Setting
230 / 400 V
57 / 100 V
47,50 Hz
49,80 Hz
0,20 s
0,08 s
0,10 s
0,12 s
0,00 Hz
0,05 Hz
K1, K2
--
50,05 Hz
51,00 Hz
0,20 s
0,12 s
0,10 s
0,12 s
0,00 Hz
0,05 Hz
K1, K2
--
51,50 Hz
52,00 Hz
0,20 s
0,12 s
0,10 s
0,12 s
0,00 Hz
0,05 Hz
K1, K2
--
8 °
8 °
3-phase
3-phase
5,00 s
1 s
1,00 s
1 s
--
--
45 / 80 V
12 / 20 V
0,10 s
0,1 s
0,10 s
0,1 s
5 / 10 V
2 / 2 V
--
--
--
--
3-/ 4-Wire
3-/ 4-Wire
K1, K2
--
30 s
--
K1, K2
--
on
--
on
--
on
--
0
0
on
off
000
000
10
10
0
0
Page 15
Customers
Dim
Setting Value
Hz
s
s
Hz
Hz
s
s
Hz
Hz
s
s
Hz
°
s
s
V
s
s
V
s