Daikin VRVIII Series Handbuch Technische Daten - Seite 19

Blättern Sie online oder laden Sie pdf Handbuch Technische Daten für Klimagerät Daikin VRVIII Series herunter. Daikin VRVIII Series 20 Seiten. Air conditioning systems bs box
Auch für Daikin VRVIII Series: Handbuch Technische Daten (18 seiten), Handbuch Technische Daten (20 seiten), Handbuch Technische Daten (11 seiten)

Daikin VRVIII Series Handbuch Technische Daten
11
Junction box - BEVQ-MAVE

11 - 4 Wiring diagram

BEVQ-MA
3
Control box
A1P
A2P
F1U
HAP
R3T
: Terminal
: Connector
: Field wiring
NOTES
1
TThis wiring diagram only shows the BEV unit. See the wiring diagrams and installation manuals for the wiring and settings for the indoor, outdoor, and BS units.
2
See the indoor unit's wiring diagram when installing optional parts for the indoor unit.
3
Only one indoor unit may be connected to the BEV unit. See the indoor unit's wiring diagram when connecting the remote control.
4
Always use the sky air connection adapter for the indoor unit when using a central control unit. Refer to the manual attached the unit when connecting.
5
Cool/Heat changeover of indoor units connected to BEV unit cannot be carried out unless they are connected to BS unit.
In cas of a system with BEV unit only, Cool/Heat selector is required.
6
Set the SS1 tot "M" only for the BEV unit connected to the indoor unit which is to have Cool/Heat switching capability, when connecting the BS unit.
The "M/S" on the SS1 stands for "Main/Sub".
This is set to "S" when shipped from the factory.
7
Connect the attached thermistor to the R3T.
18
• Indoor Units • 4-WAY BLOW CEILING SUSPENDED CASSETTE • BEVQ-MAVE
Printed circuit board Assy
Power supply printed circuit board Assy (220-240V/16V)
Fuse ( , 10A/250V)
Light emitting diode (Service monitor-green)
Thermistor (Gas)
• VRV Systems • Indoor Units
To outdoor unit
SS1
Selector switch (M/S)
X1M
Terminal strip (Power)
X2M
Terminal strip (Transmission)
Y1E
Electronic expansion valve
Z1C ~ Z3C / Z4F
Noise filter
COLORS :
BLU : Blue
RED : Red
WHT : White
BLK : Black
Power Supply
50
60
~
~
220-240V
220V
To indoor unit
Note 4
To interface adaptor for sky
air series of indoor unit.
3D044901B