START-UP PROCEDURE

OPERATING MANUAL - ARID-X, HP4-X 18-100 FM DRYERS
Revision 10/8/02
DRI-AIR
INDUSTRIES, INC.

Standard Electrics

Operating this unit is very simple. Once the dryer is
connected to the facility power supply, the unit can be started
by turning the disconnect located on the electrical panel
enclosure to the ON position and pressing the ON button on
the Control Panel Key Pad. To shut the dryer off, simply push
the OFF button on the Control Panel Key Pad and turn the
disconnect to the OFF position.
Setting the process air temperature is done using the Digital
Controller.
For a more detailed explanation, see the following sections.
Control Panel - Operating Display
Turn power on to dryer using disconnect.
1. POWER light indicates power to the unit is on.
Press ON button on key pad.
2. Illuminated BLOWER Light indicates Blower is on.
3. Flashing ZONE light indicates bed is in Regeneration
cycle.
4. Steady ZONE light means bed is in cooling cycle.
5. Illuminated HEATER light indicates heater is on.
Alarm Conditions:
6. Flashing HIGH TEMP. ALARM indicates an over or
under temp alarm. Unit shuts down.
7. Steady HIGH TEMP. ALARM light indicates a
thermocouple has failed. Further diagnostics are
required.
8. Flashing ALARM light indicates a safety override
condition has occured. Dryer shuts down.
Digital Controller - Setting Process Air Temperature:
Press SET button - temperature set display will flash.
Press up arrow to increase temperature and down arrow to
decrease temperature.
Press SET again to enter the new temperature.
If the display flashes, the temperature is out of the control
range.
If the display shows 0000 the thermocouple is not connected
or is faulty.