100, 200, 500, 700, & FMA Series
12. Floor Installation
CAUTION: Ensure adequate manpower is available to help safely install the Product. Empty cabinets alone may weigh up to 200 lbs. Moving rack
cabinets can present dangers to both personnel and the installed equipment.
CAUTION: Use eye protection and protective gloves while installing the cabinet.
NOTE: It is easiest to install the cabinet to the floor before loading. Be sure adequate room exists to get tooling into the bottom areas of the cabinet.
After installation to the floor, the bottom rack unit may or may not be usable. Consult Equipment Installation section.
DID YOU KNOW? In Seismic applications, the 700 Series cabinets and the Atlas Sound SBK-700 bracket kit should be utilized. With brackets properly
installed, the 700 series cabinets may support up to 625 lbs. of equipment during a Zone 4 earthquake motion, which is comparable to a Richter
Magnitude 8.0 earthquake.
a. The typical floor type for installation will be masonry. Other floor types may require floor reinforcement to support the weight of the cabinet
when fully loaded. Consult local codes for guidance.
b. Always install cabinet on a level surface, appropriately anchored in all four (4) corners. Consult drawings on AtlasSound.com for dimensions.
c. In masonry installations, use a rotary hammer drill with carbide tipped hammer drill bit to create the hole to set a wedge anchor. Atlas Sound
recommends using ITW Red Head "Multi-Set II", "Trubolt" or "Trubolt+" for seismic applications.
d. All cabinets have four (4) corner holes that will accommodate
(2) holes located in each bottom corner. FMA Series cabinets have only two (2) holes in each corner. In all cases, use
and split ring lock washers to provide addition bearing surface and vibration protection.
700 Series Bottom Cover
13. Equipment Installation
CAUTION: Ensure adequate manpower is available to help safely install equipment within the rack. Despite the small size of some gear, weights can
easily reach 80 lbs. or more. Know the weights of the equipment to be installed and use the appropriate number of people or rigging equipment.
DID YOU KNOW? Equipment installation may be greatly aided by using the Atlas Sound LAR150. The LAR150 Load-A-Rack tool provides a
much-needed helping hand during installation and reduces manpower needed to hold the equipment in place during installation.
DID YOU KNOW? Rail positions (rack units) are conveniently marked on the cabinet rails. The 1st position will always be at the bottom of the cabinet.
The first set of 3 mounting holes in each rail make-up this 1st rack unit position. The next set of 3 mounting holes make-up the 2nd rack unit position
and so on.
NOTE: Interference could exist between racked-equipment, doors, and floor of the cabinet. See Initial Rail Setup section before proceeding.
a. Equipment is typically mounted using 10-32 screws.
b. Start mounting equipment in the lower elevations of the cabinets.
c. Always mount the heaviest equipment within the lower elevations of the cabinet.
NOTE: If installed equipment has cooling vents on the top or bottom, do not block those vents. Leave at least 1RU of space or more between
adjacent equipment. Filler panels may be used to fill these open spaces.
1601 JACK MCKAY BLVD.
ENNIS, TEXAS 75119 U.S.A.
Floor-Standing Cabinets
⁄
-18 grade 5 hardware. The 700 Series cabinets also have an additional two
5
16
100, 200, 500 Series Bottom Cover
TELEPHONE: (800) 876-3333
FAX: (800) 765-3435
⁄
" fender washers
5
16
FMA Series Bottom Cover