DIF-PUR does not require any maintenance except for external cleaning and filter replacement when
saturated or damaged.
It is important to keep the discharge grille clean, to not obstruct the flow of air from the unit. When cleaning,
care must be taken when passing a damp cloth as the grille rests thanks to two angles on each side. If the
grille is pressed up, we will disengage it from its place, which means that the grille must be completely
removed to make the cleaning or hold it with one hand while cleaning with the other hand.
Cleaning from the outside should be done with a damp cloth and a conventional detergent. Do not use
caustic or acid-containing detergents.
For safety, before cleaning, turn off the appliance using the controller.
Repairs and handling of the equipment must be carried out exclusively by
authorized personnel.
It is forbidden to open the service panel without disconnecting the power (risk of
electric shock and fan entrapment).
The inside of the appliance must not be cleaned with water or steam.
To remove the filters, open the fence and move the safety angle that holds each filter and replace them with
the new filters:
The assembly and electrical connection must be carried out exclusively by specialized
personnel and observing these instructions.
Before performing any repair, you must:
• Notify staff and indicate that work is being made.
• Disconnect the current and protect the thermal magnet (so that no one can inadvertently
operate it).
• Make sure there is no voltage in the equipment.
• Make sure the fans have stopped.
• Use only original spare parts.
To remove the gate simply tilt it from one side and make a little game to remove it from the inside of the
equipment.
Once the process is complete, there is access to the absolute filter and fan.