BECKWITH ELECTRIC Syncrocloser M-3410A Handbuch - Seite 14

Blättern Sie online oder laden Sie pdf Handbuch für Kontrollsysteme BECKWITH ELECTRIC Syncrocloser M-3410A herunter. BECKWITH ELECTRIC Syncrocloser M-3410A 18 Seiten.

BECKWITH ELECTRIC Syncrocloser M-3410A Handbuch
M‑5625 Digital Synchronizing System
Radiated Susceptibility
ANSI/IEEE
80-1000 Mhz @ 35 V/m (with Keying test)
C37.90.2
2004
Output Contacts
ANSI/IEEE
Make 30 A for 0.2 seconds, off for 15 seconds for 2,000 operations
C37.90.0
Section 6.7.1, Tripping Output Performance Requirements

Atmospheric Environment

Temperature
IEC 60068-2-1
Cold, –20° C
IEC 60068-2-2
Dry Heat, +70° C
IEC 60068-2-78 Damp Heat, +40° C @ 93% RH

Mechanical Environment

Vibration
IEC 60255-21-1
Vibration response Class 1, 0.5 g
Vibration endurance Class 1, 1.0 g
IEC 60255-21-2
Shock Response Class 1, 5.0 g
Shock Withstand Class 1, 15.0 g
Bump Endurance Class 1, 10.0 g
Compliance
UL
Listed per 508 – Industrial Control Equipment certified for Canada CAN/CSA C22.2 NO. 14-M91
c
us
UL
Listed Component per 508A Table SA1.1 Industrial Control Panels
c
us
Physical
19" Rack Mount
Size: 10.50" high x 19.0" wide x 14.00" deep (26.7 cm x 48.26 cm x 35.56 cm)
Approximate Weight: 36 lbs, (16.33 kg)
Approximate Shipping Weight: 53 lbs, (24.04 kg)
Vertical Panel Mount
Size: 19.00" high x 10.50" wide x 14.00" deep (48.26 cm x 26.7 cm x 35.56 cm)
Approximate Weight: 36 lbs, (16.33 kg)
Approximate Shipping Weight: 53 lbs, (24.04 kg)
Patent & Warranty
The M-5625 Syncrocloser
The M-5625 Syncrocloser
date of shipment.

External Connections

M-5625 external connection points are illustrated in Figure 5, External Connections.
Digital Synchronizing System is covered by U.S. Patent 3,491,248.
Digital Synchronizing System is covered by a five year warranty from
–14–