Installation Process (continued)
4. Rotate the mounting feet in and insert the box into
the hole.
5. Tighten the Phillips head screws until the box is secure.
Note: Do not overtighten screws. Ceiling access is not
necessary for installation. Be sure the label is visible after
mounting the recessed box.
6. Install the batteries in the orientation (+ -) shown on the
bottom of the battery compartments.
7. Secure the sensor to the ceiling by twisting it onto the base.
8. After the batteries have been installed for at least
3 minutes, initiate the Installation Test Mode: Momentarily
press the Utility button. The green LED flashes once then
the red LED flashes each time the sensor detects motion.
(The test mode times out after 5 minutes).
A. Walk test the sensor. Walk outside the coverage
area and wait for the red LED to stop flashing.
Step inside the desired coverage area and observe
the red LED.
B. Repeat from various positions in the coverage area.
C. If necessary, adjust the sensor as described in
PIR Sensitivity Adjustment. Repeat the walk test.
D. If you do not observe the proper behavior,
see Troubleshooting.
9. Exit Installation Test Mode. Momentarily press the Utility
button again, or wait 5 minutes for the mode to time out.
10. Complete the installation by resetting the device: press and
hold the Utility button for 5 seconds. Release the button when
the Network LED begins to flash rapidly. The sensor attempts
to join a ZigBee network for up to 30 seconds.
See LED Operation and Joining the ZigBee Network.
2
LED Operation
Green LED:
Network Indicator
Rapid flash (12 times
per second) for up to 30
seconds
Solid for 10 seconds
Flashes once
Flashes twice
On for 2 seconds every
30 seconds
Red LED: Installation
Test Mode, Motion
While unit is in
Installation Test Mode,
Flashes
Off
2
Installation Guide
Description
Device is trying to join ZigBee
network. If it fails to join, it will
retry after 15 minutes.*
Device successfully joined a ZigBee
network.
Utility button was pressed to initiate
Installation Test Mode.
Utility button was pressed for
2 seconds and the device is currently
joined to a network.
The batteries are low; replace the
batteries. Will also generate low
battery warning within CSM.
Description
The red LED flashes each time sensor
detects occupancy. Test mode times
out after 5 minutes.
Normal operation: either not
detecting occupancy, or detected
occupancy and in Off Delay. LED
turns on with initial occupancy.