General Installation Instructions
These instructions should be read carefully prior to any installation and retained after completion for further reference and
maintenance. Please give these instructions to the building owner/occupier after installation.
Important Safety
1.
Before installation, maintenance or lamp replacement, ensure that the mains supply to the luminaire is switched off and
the circuit supply fuses are removed or the circuit breaker is turned off.
2.
It is recommended that only a qualified electrical contractor carries out the installation of this luminaire and that the
luminaire is installed in compliance with the current edition of the IEE Wiring Regulations.
3.
The person carrying out the installation is to check and verify that the total load on the circuit, including that of this
luminaire does not exceed the rating of the circuit cable, fuse or circuit breaker.
4.
Where a luminaire incorporates discharge control gear (inductive load), the circuit capacity and ratings require careful
sizing to avoid nuisance tripping of the protective device used in the installation.
5.
Where applicable, careful consideration should be taken during installation to ensure that all fixings and/or suspensions
are of a suitable size for the luminaire being installed.
Ratings
1. All luminaires are manufactured & tested in compliance with the requirement contained within BS EN 60598 and are CE marked.
2. All luminaires that are of Class 1 construction and that are marked accordingly, MUST be earthed.
3. All luminaires are designed to operate at 230Volts AC -6%/+10% = 216Volts to 252Volts. Do not operate outside these voltages.
4. All luminaires are only suitable for applications within their rated Ingress Protection limits as stated.
5. This luminaire is designed for internal use only.
Exclusions to Warranty
Please Note - The limited warranty shall be null and void in the following circumstances:-
Failure by the installer, end user or any third party to exercise caution to protect any covered product or part from outside damage, adverse temperature (normal operating
ambient temperature 0 - 25°C), humidity conditions, fluctuations in the electrical system or physical abuse as well as failure related to workmanship in the installation of
the products or parts.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Installation
Select a suitable mounting location to install luminaire. Check that sufficient depth is available in the ceiling void and there is adequate free air
ventilation around the luminaire.
Luminaire should not be mounted facing any combustible material within 500mm.
Cut a125mm for AULED125D or 150mm for AULED150D diameter aperture in ceiling material. If required, maintain any fire barrier by
installation of suitable fire hood available from Ansell Lighting.
Connected to supply cable to the Wieland connector (supplied), taking care to observe the correct polarity (please see electrical connections
below). This fitting is Class I and does require an earth connection.
During connection of the remote gear to the luminaire the supply must only be initiated after the connection of the male and female connectors.
Do not connect the luminaire to the driver if the driver has an incoming supply. This can damage the LED.
Do NOT cover the remote control gear with thermal insulation or any other material.
Connect as follows:-
Plug high-tension cable and plug into the corresponding socket on the fitting, ensuring the plug is pushed fully home. Do not install the luminaire
onto new plaster or wet paint.
Offer the remote gear fitting through the aperture and bend back the two spring tabs. Release tabs and allow fitting to be drawn into place.
Angle the head into the desired position for version
Restore mains supply, switch on and test for satisfactory operation.
-
Luminaire not suitable for covering with thermally insulating material.
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Maintenance:
1. This luminaire LED contains no serviceable parts.
Disposal of Electronic Equipment WEEE Directive 2002/96/EC
This product falls within the scope of the Waste Electrical & Electronic Equipment Directive
(WEEE), which means the product should not be disposed of as normal household waste.
Ensure that this luminaire and lamp is disposed of in accordance with the WEEE Directive.
Contact a local Council Waste Dept. Local Amenity Site, or the Environment Agency for
further information. RoHS - All components and materials used in this product are RoHS
2002/95/EC compliant.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Description – Unity LED Downlight - Emergency
Installation Instructions
Luminaire Code(s) –
PERMANENT LIVE
(L2)
SWITCHED LIVE
(L1)
NEUTRAL
(N)
EARTH
IP44
www.anselluk.com
AULED125D/M3, AULED150D/M3
BROWN OR RED
BLUE OR BLACK
BLUE OR BLACK
GREEN / YELLOW