DSC Acuity AMA-100 Einbauanleitung - Seite 3
Blättern Sie online oder laden Sie pdf Einbauanleitung für Sicherheitssensoren DSC Acuity AMA-100 herunter. DSC Acuity AMA-100 4 Seiten. Addressable glass break detector
Wiring the Device
To connect the AMA-100, consult the wiring diagram below:
Mounting the AMA-100
Once the location has been determined, open the detector by pressing the
release tab on the bottom with a small flat-blade screwdriver. Remove the cover
and set in a safe location. Draw the wires through the rectangular opening in the
backplate and connect to the terminal block. Mount the detector using the two
mounting screws. Once the device is wired and mounted, you will need to enroll it.
Device Enrollment
The serial number located on the back of the device must be enrolled into the
alarm control panel via Installer's Programming ([ ] [8] [Installer's Code]). This
procedure is outlined for the PC4010/4020 in the control panel Installation
Manual and for the Power panels in the PC5100 Installation Manual.
Once the detector is enrolled, replace the cover and test the detector using the
AFT-100 tester to confirm proper operation.
WARNING: Connect only DSC Addressable Series devices to the
addressable loop connections. Connection of ANY other type of device will
impair operation. Any devices other than Addressable Series devices which
require power to operate must be powered separately.
Testing
Once you have mounted, wired and enrolled the detector, test to ensure that
the detector is working correctly. To do this:
1. Put the control panel in walk test mode as described in the control panel
installation manual.
2. Use the AFT-100 glass break simulator to test the AMA-100. When the AMA-
100 is working correctly, the LED will light up in response to the AFT-100.
Refer to the section below for tips on using the AFT-100.
3. End walk test mode as described in the control panel installation manual.
NOTE: The detector will not respond to the glass break simulator unless the
system is in walk test mode.
The AFT-100 Glass Break Simulator
The AFT-100 glass break simulator generates plate or tempered glass samples.
Use the plate glass setting if you are unsure of the glass type. Observe the
following when testing the detector:
• The correct mounting location is indicated by three successive detections. If the
detector does not respond each time, relocate the detector and repeat the test.