Program Descriptions
S
The following section explains all the programmable features including how the feature operates,
options that pertain to the feature and a summary of the program locations required for programming.
5.1
Station Definitions
Each station must be defined for proper operation. The options are as follows:
• Option [00] - Not Used
• Option [01] - Doorbox 1
• Option [02] - Doorbox 2
All unused stations should be defined as [00]. Only exterior boxes should be defined as
doorbox 1 or doorbox 2. Only one station can be defined as Music Input. All other stations
should be defined as [03].
Station Definitions .......................................... Section [01]
5.2
Zone Port Assignment
When the Talk/Listen-In feature operates the panel will automatically turn on the station closest
to the alarm. For this to operate properly you must program the Zone Port Assignment to
program which zone is closest to which station. When the communication link is established
the central station operator will hear input from the station closest to the alarm.
Zone Port Assignments must be programmed even if zone alarms are not used.
Tampers, Openings and Closings, and all other events will not function if there
are NO ports assigned here.
Zone Port Assignment ................................... Section [10] to [13]
5.3
Keypad Port Assignment
This section is used to program which keypad is closest to which station. This is used with
the Identified Voice Prompted Help feature described in Section 3.12.
5.4
Broadcast Mask
There may be situations when a station will only be used to initiate Pages. If the Broadcast
Mask option for the station is disabled it will not enunciate any incoming tones except
telephone rings (if enabled). The Do Not Disturb light will remain on at all times.
If incoming tones are disabled, the station can still be used to answer pages, doorbells and
incoming calls.
Broadcast Mask ............................................. Section [20]
5.5
Alarm Follower
The stations can be used to sound alarm conditions along with the Bell Output of the
Power832 PC5010 control panel. If the Local Alarm Follower option is enabled all stations
will sound tones using Burglary and Fire type tones. If disabled the stations will not
enunciate alarms. All Burglary alarms will sound a "steady" alarm output. All Fire alarms will
sound a "pulsed" alarm output.
E
C
T
I
• Option [03] - Intercom
• Option [05] - Music Input
9 9