DSC FSA-410AT Installations- und Betriebsanleitung - Seite 4

Blättern Sie online oder laden Sie pdf Installations- und Betriebsanleitung für Rauchmelder DSC FSA-410AT herunter. DSC FSA-410AT 4 Seiten. Fsa-410 series smoke detector

DSC FSA-410AT Installations- und Betriebsanleitung
Smoke Detector Family
4-Wire Smoke Detector Family
FSA-410 XYYYY
L = Remote LED output
R = Auxiliary Form C Relay
S = Sounder
T = Fixed Temperature Heat Sensor
Model
FSA-410A, FSA-410B, FSA-410C
FSA-410AT, FSA-410BT, FSA-410CT
FSA-410AR, FSA-410BR, FSA-410CR
FSA-410ART, FSA-410BRT, FSA-410CRT YES
FSA-410AS, FSA-410BS, FSA-410CS
FSA-410AST, FSA-410BST, FSA-410CST YES
FSA-410ARS, FSA-410BRS, FSA-410CRS
FSA-410ARST, FSA-410BRST, FSA-
410CRST
FSA-410ALST, FSA-410BLST, FSA-
410CLST
FSA-410ALRST, FSA-410BLRST, FSA-
410ClRST

Specifications

Diameter (base) ........................................................... 5.8in (147mm)
Height (including base) ............................................. 2.077in (528mm)
Operating Temperature...................................... 32º-100ºF (0º-37.8ºC)
Humidity............................................... 5%-93% RH, non-condensing
Operating Voltage Range.....................................................10-30 V
Maximum Standby Current................................... 20µ µ A@12 or 24V
Maximum Alarm Current .................................................25mA-90mA
Smoke Sensitivity ULC................................. 2% ± 0.5%/ft obscuration
Smoke Sensitivity UL ................................... 3% ± 0.8%/ft obscuration
Heat Alarm ..................................................................... 135ºF (57ºC)
Sounder Alarm Pattern ULC..................................... Continuous Beeps
Sounder Alarm Pattern UL ....................... Evacuation Temporal Pattern
Minimum Remote LED Resistance:
12V system........................................................................ 500 Ohm
24V system...................................................................... 1000 Ohm
Maximum Remote LED output (if equipped)............................... 25mA
Auxiliary Relay Rating (Form C Relay) ................2A @ 30V
Alarm Relay Rating (Form A Relay) .................2.0A @ 30V
A = ULC
{
B = UL
C = EU
Aux
LED
Heat Sounder
Relay
Output
NO
NO
NO
NO
YES
NO
NO
NO
NO
NO
YES
NO
NO
YES
NO
NO
YES
NO
NO
YES
NO
NO
NO
YES
YES
NO
YES
YES
YES
NO
YES
YES
NO
YES
YES
YES
YES
YES
DC
DC
Limited Warranty
Digital Security Controls Ltd. warrants that for a period of twelve months from the date of pur-
chase, the product shall be free of defects in materials and workmanship under normal use and
that in fulfillment of any breach of such warranty, Digital Security Controls Ltd. shall, at its
option, repair or replace the defective equipment upon return of the equipment to its repair depot.
This warranty applies only to defects in parts and workmanship and not to damage incurred in
shipping or handling, or damage due to causes beyond the control of Digital Security Controls
Ltd. such as lightning, excessive voltage, mechanical shock, water damage, or damage arising
out of abuse, alteration or improper application of the equipment.
The foregoing warranty shall apply only to the original buyer, and is and shall be in lieu of any
and all other warranties, whether expressed or implied and of all other obligations or liabilities on
the part of Digital Security Controls Ltd. Digital Security Controls Ltd. neither assumes respon-
sibility, nor authorizes any other person purporting to act on its behalf to modify or to change this
warranty, nor to assume for it any other warranty or liability concerning this product.
In no event shall Digital Security Controls Ltd. be liable for any direct, indirect or consequential
damages, loss of anticipated profits, loss of time or any other losses incurred by the buyer in con-
nection with the purchase, installation or operation or failure of this product.
Smoke Detectors
Smoke detectors that are a part of this system may not properly alert occupants of a fire for a num-
Max.
ber of reasons, some of which follow. The smoke detectors may have been improperly installed or
Alarm
positioned. Smoke may not be able to reach the smoke detectors, such as when the fire is in a chim-
Current
ney, walls or roofs, or on the other side of closed doors. Smoke detectors may not detect smoke
Draw
from fires on another level of the residence or building.
Every fire is different in the amount of smoke produced and the rate of burning. Smoke detectors
25mA
cannot sense all types of fires equally well. Smoke detectors may not provide timely warning of
fires caused by carelessness or safety hazards such as smoking in bed, violent explosions, escaping
25mA
gas, improper storage of flammable materials, overloaded electrical circuits, children playing with
matches or arson. Even if the smoke detector operates as intended, there may be circumstances
40mA
when there is insufficient warning to allow all occupants to escape in time to avoid injury or death.
40mA
WARNING: Digital Security Controls Ltd. recommends that the entire system be completely
tested on a regular basis. However, despite frequent testing, and due to, but not limited to,
75mA
criminal tampering or electrical disruption, it is possible for this product to fail to perform as
expected.
75mA
Important Information: Changes or modifications not expressly approved by Digital Security
90mA
Controls Ltd. could void the user's authority to operate this equipment.
90mA
FCC Compliance Statement
CAUTION: Changes or modifications not expressly approved by DSC could void your author-
ity to use this equipment.
75mA
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
90mA
against harmful interference in a residential installation. This equipment generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause harmful inter-
ference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following
measures:
• Re-orient the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
DC
• Consult the dealer or an experienced radio/television technician for help.
The user may find the following booklet prepared by the FCC useful: "How to Identify and
DC
Resolve Radio/Television Interference Problems". This booklet is available from the U.S. Gov-
ernment Printing Office, Washington D.C. 20402, Stock # 004-000-00345-4.
Industry Canada Compliance Statement
This Class B digital apparatus meets all requirements of the Canadian interference-causing
equipment regulations.
Cet appareil numérique de la Classe B respecte toutes les exigences de règlement sur le matériel
brouilleur du Canada.
(Resistive)
(Resistive)
©2003 Digital Security Controls
Toronto, Canada • www.dsc.com
Technical Support: 1-800-387-3630 (Canada & U.S.) or 905-760-3036
Printed in Canada
2 9 0 0 6 0 1 9 R0 0 3