DSC Maxsys PC4612 Einbauanleitung - Seite 2
Blättern Sie online oder laden Sie pdf Einbauanleitung für Rauchmelder DSC Maxsys PC4612 herunter. DSC Maxsys PC4612 2 Seiten. Fire zone annunciator
1
Choose the output to be programmed (01-16)
2
Enter the number of the output option to be used for
that output.
3
To exit, press [#].
The recommended output options for the PC4612(A) are (22),
(48), (55), (56), (57). Their descriptions are listed below.
4.3 Recommended Output Options
Zone Follow (22)
For zones that are programmed as Fire or Fire Supervisory,
the zone follow output will turn on the LED when the fire
zone is in alarm, or when the fire supervisory zone is off-
normal (zone shorted). The LED will only turn off when the
zone has been restored and a fire reset has been performed.
Use this option for PC4612(A) output numbers 01 - 12.
Outputs 1-10 have red LEDs and are intended for fire alarm
zone annunciation. Outputs 11-12 have yellow LEDs and are
intended for fire supervisory zone annunciation.
Use only the red LEDs for fire alarms and only the yellow
LEDs for fire supervisory. This annunciator is intended for
fire related outputs only. Do not use the module for other
kinds of system annunciation.
Fire Zone Tbl. (48)
The output will activate when a fire zone is bypassed, or when
a fire zone trouble condition is detected. The output will
deactivate when the zone is unbypassed or the trouble is
restored. Use this option for PC4612(A) output number 13.
Common Fire Tbl. (55)
The output activates when any of the following troubles are
PC4612(A) Programming
[000703XX]
PC4216 Options
Custom Group No.:
[000704XXYY]
PC4216 Custom
Output
PC4612LED
No.
1
1
2
2
3
3
4
4
For
5
5
Fire Zones
6
6
(Red)
7
7
8
8
9
9
10
10
For Fire
11
11
Supervisory
12
12
(Yellow)
13
Zone Trouble
14
Bell Trouble
15
System Trouble
16
AC On
©1999 Digital Security Controls Ltd.
TM
1645 Flint Road, Downsview, Ontario, Canada M3J 2J6
Security Products
(416) 665-8460 • Fax (416) 665-7498 • 1-800-387-3630 • www.dscgrp.com
PC4612(A) Module No.:
NOTE: XX = module # (Enter 01 - 09)
l _ _______l _ _______l
l _ _______l _ _______l
l _ _______l _ _______l
l _ _______l _ _______l
l _ _______l _ _______l
NOTE: XX = custom group # (Enter 01 - 09); YY = output # (Enter 01-16)
Recommended
Option
22
22
22
22
22
22
22
22
22
22
22
22
48
56
Yellow
55
Green
57
detected by the panel. The output deactivates when the
trouble is cleared:
¨ Any system AC or battery trouble (PC4020, PC4820,
PC4204, PC4701)
¨ Any system communicator trouble (TLM1, TLM2, FTC,
LINKS)
¨ Ground Fault trouble
Use this option for PC4612(A) output number 15.
Bell Trouble (56)
The output activates for a trouble (open or short) on any
supervised system bell output (PC4010/4020 or PC4702). The
output deactivates when the trouble is cleared. Use this option
for PC4612(A) output number 14.
AC Status (57)
The output will be ON when AC power is present on the
PC4010/4020, as well as all enrolled modules (PC4204, PC4820,
PC4702). If the PC4010/4020 or any module loses AC power,
the AC Fail Delay timer will start (see your PC4010/4020
Installation Manual for more information). When the timer
expires (or if it is programmed to be 0), if the AC is still missing,
the output will turn OFF. An AC Fail trouble condition will be
generated. When AC power is restored, the output will again
wait for the AC Fail Delay timer to expire. If the AC power is
still on at the end of the delay, the output will turn ON. Use this
option for PC4612(A) output number 16.
4.4 Finishing
Make sure you label each of the 12 zone lights in the space
provided on the annunciator. When you have finished installing
and programming the PC4612(A), instruct the end-user of the
system how to interpret events using the annunciator.
l _ _______l _ _______l
Output
Zone
Option
Select Zone 001-128 (PC4020), 001-064 (PC4010)
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I _ _ _ _ __ _ I
Select Zone 001-128 (PC4020), 001-064 (PC4010)
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I _ _ _ _ __ _ I
Select Zone 001-128 (PC4020), 001-064 (PC4010)
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I _ _ _ _ __ _ I
Select Zone 001-128 (PC4020), 001-064 (PC4010)
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I _ _ _ _ __ _ I
Select Zone 001-128 (PC4020), 001-064 (PC4010)
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I _ _ _ _ __ _ I
Select Zone 001-128 (PC4020), 001-064 (PC4010)
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I _ _ _ _ __ _ I
Select Zone 001-128 (PC4020), 001-064 (PC4010)
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I _ _ _ _ __ _ I
Select Zone 001-128 (PC4020), 001-064 (PC4010)
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I _ _ _ _ __ _ I
Select Zone 001-128 (PC4020), 001-064 (PC4010)
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I _ _ _ _ __ _ I
Select Zone 001-128 (PC4020), 001-064 (PC4010)
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I _ _ _ _ __ _ I
Select Zone 001-128 (PC4020), 001-064 (PC4010)
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I _ _ _ _ __ _ I
Select Zone 001-128 (PC4020), 001-064 (PC4010)
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I
I _ _ _ _ __ _ I _ _ _ _ __ _ I