2.7 BATTERY
A. The UPS module shall use a valve regulated sealed Lead Calcium heavyduty industrial
battery, designed for auxiliary power service in a UPS application. The primary battery
shall be furnished with battery with impact resistant plastic case and housed in matching
battery cabinet (s).
1. Protection against Deep Discharge and Self-Discharge: The UPS shall be equipped with
a device designed to protect the battery against deep discharge depending on discharge
conditions, with isolation of the battery by a circuit breaker. In particular, a monitoring device
shall adjust the battery shutdown voltage as a function of a discharge coefficient to
avoid excessive discharge.
2. Battery Self-Tests: The battery monitoring system shall be to perform the following auto-
matic functions:
a. Battery circuit check
b. Partial discharge test customer selectable (LCD model only).
2.8 External Maintenance Bypass (Optional):
The maintenance bypass provides a wrap around bypass configuration for total UPS iso-
lation during maintenance. Maintenance bypass transfers shall be without interruption and
shall have mechanical interlocks to protect the UPS from damage in the event of an out of
sequence transfers.
PART 3 EXECUTION
3.1 SITE TESTING START-UP
A. The UPS system will be checked, start-up and tested by a manufacturer's qualified field
service engineer.
3.2 MAINTENANCE TRAINING
A. The manufacturer shall make available to the customer various levels of training ranging
from basic UPS operation to UPS maintenance.
END OF SECTION