3onedata IES618-2F-4DI Handbuch zur Schnellinstallation - Seite 3
Blättern Sie online oder laden Sie pdf Handbuch zur Schnellinstallation für Schalter 3onedata IES618-2F-4DI herunter. 3onedata IES618-2F-4DI 4 Seiten. Managed industrial ethernet switch
【Console Port Connection】
The device provides 1 RS232-based procedure debugging
port, and can manage the CLI command line of the device
after connected to PC. The interface adopts RJ45 port, the
RJ45 pins definition as follows:
Pin No.
2
3
Definition
TXD
RXD
【Checking LED Indicator】
The function of each LED is described in the table as below:
LED
Status
Description
Power supply is connected and
ON
running normally
P1/P2
Power supply is disconnected
OFF
and running abnormally.
Power supply and port link
ON
alarm
ALM
Power supply and port link
OFF
without alarm
The device is powering on or
ON
abnormal
The device is powered off or
RUN
OFF
abnormal
Blink once per second, the
Blinking
device is running well.
Ethernet port has built valid
ON
connection
Link/Act
Ethernet port is in an active
Blinking
(1-8)
network status
Ethernet port has not built valid
OFF
connection
TX
Blinking
Serial port is sending data
(1-4)
OFF
Serial port is not sending data
Blinking
Serial port is receiving data
RX
Serial port is not receiving data
(1-4)
OFF
or serial port is not connected
【Logging in to WEB Interface】
This device supports WEB management and configuration.
Computer can access the device via Ethernet interface. The
way of logging in to device's configuration interface via IE
browser is shown as below:
Step 1
Configure the IP addresses of computer and the
device to the same network segment, and the
5
network between them can be mutually accessed.
GND
Step 2
Enter device's IP address in the address bar of the
computer browser.
Step 3
Enter device's username and password in the login
window as shown below.
Click "OK" button to login to the WEB interface of
Step 4
the device.
Note:
The default IP address of the device is "192.168.1.254".
The default username and password of the device is
"admin".
If the username or password is lost, user can restore it to
factory settings via device DIP switch or management
software; all modified configurations will be cleared
after restoring to factory settings, so please backup
configuration file in advance.
Please refer to user manual for specific configuration
method of logging in to WEB interface and other
configurations about network management function.
【Specification】
Panel
10/100Base-T(X) RJ45,
automatic flow control, full/half
100M copper port
duplex mode, MDI/MDI-X
autotunning
100M fiber port
100 Base-FX
Rs-232 DB9 interface or
Serial port
RS-485/422 terminal
CLI command management port
Console port
(RS-232), RJ45
2-pin 7.62mm pitch terminal
blocks, support 1 channel relay
Alarm interface
alarm information output, current
loading capability of
1A@24VDC or 0.5A@120VAC
Running indicator, interface
Indicator
indicator, power supply indicator
and alarm indicator
Exchange attributes
Backplane bandwidth
2G
Packet buffer size
1Mbit
MAC table size
2K
Power supply
Input voltage of power supply:
12~48VDC
Input power supply
Support DC dual power supply
redundancy, anti-reverse
connection
4-pin 7.62mm pitch terminal
Access terminal
blocks
Consumption
No-load: 4.80W@24VDC
Model I
Full-load: 6.90W@24VDC