Auber Instruments SYL-2381-SSR Gebrauchsanweisung - Seite 6

Blättern Sie online oder laden Sie pdf Gebrauchsanweisung für Controller Auber Instruments SYL-2381-SSR herunter. Auber Instruments SYL-2381-SSR 6 Seiten. Pid temperature controller

AUBER INSTRUMENTS
a. Wiring diagram
L1
240VAC
L2
Figure 11. Typical wiring set up for beer brewing and bird incubator. For smoker
control, the RTD sensor should be replaced by K type thermocouple
b. Parameter setting. These are the parameters that need to be changed from the
initial value:
Inty = P10.0, SV = 150.0° F, AH1 = 155.0° F, AL1 = 154.0° F
outy = 1, coty = SSR for PID mode with SSR output.
If the default PID settings are not good for you, please try to use Auto-tune to
optimize the PID settings: power up the controller. Press and hold the ">" key until
"AT" starts to blink. The controller starts the Auto-tuning. When the "AT" stops
blinking, the new PID parameters are generated for the system. The controller is
in normal operation mode. The tank will be maintained at 150.0 ° F.
Please note that you don't not have to wire or set the alarm to control the
temperature.

11. Error Message and Trouble Shooting

11.1 Display EEEE
This is an input error message. The possible reasons are, the sensor is not
connected correctly; the input setting is wrong type; or the sensor is defective. If
this happens when using thermocouple sensor, you can short terminal 9 and 10
with a copper wire or paper clip. If then the display shows ambient temperature,
the thermocouple is probably defective. If this happens when using the RTD sensor,
check the input sensor type (Inty) setting first because most controllers are
shipped with input sensor type set for type K thermocouple. Then check the wiring.
The two red wires should be on terminal 9 and 10. The clear wire should be on
terminal 8.
11.2 No output
When outy is set to 1 or 2, the control output is sent to the SSR port (pin 6 and 7).
The control output is synchronized with the OUT indicator. The flashing frequency
of the OUT light is an indication of the SSR triggering status. When OUT light is
ON, SSR should be triggered; when OUT light is OFF, SSR should be off. When
outy is set to 3 or 4, the control output is sent through J1 relay. The J1 relay action
is synchronized with the AL1 indicator. When AL1 is on, J1 relay should pull in;
when AL1 is off, J1 relay should drop out. If the control signal and the indicator are
2018.02
Heater
RTD
2
1
SSR
3
4
+ -
W
R
R
6
7
8
9
10
11
13
12
14
2
4
5
1
3
J1
Alarm1
240V buzzer
synchronized, please check whether the external device is working properly.
Please also confirm coty is set to SSR.
11.3 Poor accuracy
Please make sure calibration is done by immersing the probe in liquid. Comparing
the probe reading with a reference probe in air is not recommended because the
response time of probes can vary a lot. Different probes are designed for different
applications, and they can be quite different in their thermal mass, which will affect
their response time a lot. Some of our sensors have response time more than 10
minutes in the air. When the calibration is done correctly in liquid and the error is
5° F or larger, the most common problem for a thermocouple probe is improper
connection between the thermocouple and the controller. A thermocouple needs
to be connected directly to the controller unless thermocouple connector and
thermocouple extension wire are used. A copper connector, copper wire, or
thermocouple extension wire with wrong polarity connected on the thermocouple
will cause the reading drift more than 5° F.
Auber Instruments Inc.
5755 North Point Parkway, Suite 99,
Alpharetta, GA 30022
www.auberins.com
Tel: 770-569-8420
Copyright 2007-2018, Auber Instruments All Rights Reserved.
No part of this manual shall be copied, reproduced, or transmitted in any way without the
prior, written consent of Auber Instruments. Auber Instruments retains the exclusive rights
to all information included in this document.
WWW.AUBERINS.COM
P6/6