Auber Instruments TH100ACHIMDX Gebrauchsanweisung
Blättern Sie online oder laden Sie pdf Gebrauchsanweisung für Thermometer Auber Instruments TH100ACHIMDX herunter. Auber Instruments TH100ACHIMDX 2 Seiten. Thermometer for stove pipe, chimney, w/ remote alarm
AUBER INSTRUMENTS
Instruction Manual
1. Features
This thermometer can be used for stove pipe and chimney temperature monitoring.
The meter contains two alarm settings for the buil t -in buzzer. One can be used for high
limit alarm and the other can be used for low fuel alarm. It also has a third alarm for
the connected external buzzer that can be placed at different floor from where the
stove is located. The gauge is powered by 12V DC through an AC adapter (included)
for continuous operation. It can also be powered by car battery.
2. Specifications
AC adaptor: 100-240V, 50/60Hz input. 12 VDC, 1 Amp output.
Power consumption: <2W
Sampling rate: 4 samples/second
Accuracy: 0.2% full scale
Sensor: K type thermocouple, -320-1800° F (-200~900° C).
Output for buzzer: 12VDC, 1 Amp
LED display: 0.39 inch, red
Internal buzzer: Two set points alarm.
External buzzer: High limit or low limit alarm
Dimension: 3x5x1.2" (78x120x28.5mm)
3. Front Panel
8888
Figure 1. Front panel
AL - Internal Alarm Indicator
Value increment / Select next parameter
Value decrement / Select previous parameter
Digit shift / Internal alarm mute
Set / Confirm
OUT - External buzzer indicator
Parameter display
4. Connecting the meter
Figure 2 shows the terminals of the meter. Connect the 12V DC power adapter to the
terminal 1 and wall outlet. Connect the external buzzer connector to terminal 2. The
polarity for this socket is center pin positive (+), outer collar negative ( ). Connect the
K thermocouple to terminal 3. Please note that thermocouple connector also has
polarity. The wide blade should go to the wide slot.
2013.05
TH100ACHIMDX Thermometer
for Stove Pipe, Chimney, w/ remote alarm
Version 1.1
POWER - 12V Power supply input
OUT - Output for external buzzer
INPUT - Temperature probe input
Figure 2. Terminals (back view)
5. Parameter Setting
5.1. Temperature setting and Alarm setting (accessed by code 0001)
Table 1. Alarm parameters
Symbol
Description
SV
SV External alarm temperature
AH1
AH1 Alarm 1 on temperature
AL1
AL1 Alarm 1 off temperature
AH2 Alarm 2 on temperature
AH2
AL2
AL2 Alarm 2 off temperature
End
End
Exit
Note 1. Set Alarm for external buzzer.
There are two ways to set the external alarm temperature.
a. During the normal operation mode, press Λ or V once to swi t ch the display from
process value (PV) to set value (SV, or target temperature). The display will start to
blink. Press Λ or V again to increase or decrease the SV. When finished, wait 8
seconds and the settings will take effect automatically (the display wil l stop blinking).
b. Press SET key once. Use >, Λ and V keys to enter code 0001. Press SET key to
confi r m, then the display would be SV (Su). Press SET key again to display the SV
setting. Use >, Λ and V keys to enter the new SV value and press SET to confirm.
Press V key to change the display to END. Then, press SET to exit. You can also
ignore the steps after confirmation of SV. The controller wil l return to normal operation
mode automatically if no key is pressed for 1 minute. The flow chart below shows how
to set the SV and alarms in details.
The default setting for the external buzzer is high limit alarm (see Note 6). The external
buzzer will be on when the tempeature i s above SV+Hy (see Note 5), will be off when
the temperature drops back to SV.
Oper ation Mode
Enter Code
SET
0001
XXXX
SET
Figure 3. Flow chart for how to set target temperature and alarm.
WWW.AUBERINS.COM
Range
Arbitrary value
withi n the
measuring range
Parameter Display
External buzzer Tem
SET
SET
480
sv
Buzzer On Temp
SET
0250
ah1
Buzzer Off Temp
SET
0249
al1
Buzzer On Temp
SET
0250
ah2
Buzzer Off Temp
SET
0250
al2
end
Initial
Note
Note 1
480
Note 2
481
480
250
250
SET
SET
SET
SET
SET
P1/2