Duco DucoBox Focus 225 Installationshandbuch - Seite 6

Blättern Sie online oder laden Sie pdf Installationshandbuch für Fan Duco DucoBox Focus 225 herunter. Duco DucoBox Focus 225 16 Seiten.
Auch für Duco DucoBox Focus 225: Schnellstart-Handbuch (20 seiten)

ENGLISH
RF (wireless communication)
RF components have a maximum free-field range of 350 metres� This distan-
ce will be much less in a building because of obstacles� Therefor you will need
to allow for features such as walls, concrete and metal� All slave components
(except those which are battery powered) also act as repeaters� Signals from
components that are unable to make a (strong) connection with the master
component are forwarded automatically via no more than one other non-bat-
tery-powered component (= hop point)� Please refer to information sheet
RF communication (L8000018) at www�duco�eu for further information�
Wired (cabled communication)
Wired components can be daisy-chained (= recommended)� This means that a
separate cable will not be required for each component� A single central power
supply can be used�
The cable required is a 5 x 0�75 mm² data cable� We strongly advise using a shiel-
ded cable� This is to prevent any interference that may affect the data communi-
cation� Any Tronic grilles will be supplied with a 5 x 0�25 mm² cable which can be
connected via a splicing terminal block�

05 Control valves

The control valves, whether or not they are fitted with a sensor for measuring CO or humidity, can be built into the DucoBox Focus�
Together with the fan, they ensure the correct exhaust air flow rate in the right room�
A DucoBox Focus can contain up to a maximum of 7 control valves (= one per intake duct)� This can be expanded to a maximum of
11 control valves by using the 'Control Valve Manifold' (item 0000-4454)�
A control valve requires to be provided in every case for each ventilation duct connected!
05.A Mounting the control valves
Slide the control valve into the locations
provided in the DucoBox Focus� Connect
the 'VALVE' connector on the DucoBox
to IN on the control valve� If applicable,
connect OUT on the valve to IN on another
control valve to be added� At least one
valve must be connected to the DucoBox at
any time�
TIP: Use the letter labels on the DucoBox
and the valves (A/B/C/D/E/F/G) to give the-
se the same letter, so that the vales always
remain in the same position�
6
L2000631 Installation guide for DucoBox Focus (Revision J | 17.07.2019)
DucoBox
IN
OUT
VALVE1
IN
OUT
OUT
IN
F
E
OUT
Power supply
Wiring
Frequency
Maximum distance
Maximum number
of components
DUCO WIRED
Power supply
Wiring
Maximum distance
Maximum number
of components
IN
OUT
VALVE2
IN
OUT
G
A
B
D
C
DUCO RF
230 VAC
1,5 mm²
868 Mhz
350 m, free field (less
through obstacles)
Up to 25 wireless
components in a
single system
24 VDC
5 x 0�75 mm²
(5 x 0�25 mm² from Tronic
grilles)
up to 300 m
Up to 99 wired
components in a
single system
IN
IN
IN
IN
OUT
OUT
OUT
OUT