Installation Instructions
1. Installation Instructions
HMI is the CPI information products, may result in the use of RF interference
or electromagnetic waves are generated, may affect other appliances, the user
must ensure compliance with the following installation instructions to ensure
the correct use of safety.
1.1. Safety Precautions
You should pay attention to the following safety precautions when installation,
wiring, operation, maintenance and inspection.
1.1.1. Installation Notes
1. Following the specified instruction to install the HMI, or it may result in
equipment damage.
2.
Prohibited to let the HMI to exposure in moisture, corrosive gases,
flammable gases and other substances, or it may result in electric shock or
fire.
3. Serial communication cable and network cable and power cable should be
separated, and must be used to mask the cable, otherwise it may cause
unpredictable problems.
4. Attention! W hen drilling or work with HMI, you should not let the cut wires
or filler and other impurities fall into the HMI internal .
4. When FG terminal is connected, pleas e check if the wire is grounded
properly. Because improper grounding may result in communication error,
electric shock or fire.
1.1.5. Communication cable wiring Notes
1. Comply with communication wiring specification for wiring.
2. Restrict cable length to less than 500 '(150m) for RS485/422 devices and
50'(15m) for RS232 devices to avoid communication problems.
3. Proper grounding circuit to avoid bad communication quality.
4. Shielded cable must be used for long lengths or cables run in a n
electrically noisy environment.
5.
When wiring, should be away from AC power cable and high energy and
rapidly switching DC wiring cable.
1.1.6. Operation Notes
1. HMI should m eet the editing software to plan the screen. Un -planned HMI
may not be able start the application, or result in abnormal operation.
2. Shouldn't change the wiring when the power is turned on, or it may result
the electric shock or human injure.
3. Do not use a sharp object to touch the panel, or it may cause the panel
sunken, and thus cannot make HMI operate normally.
4. The backup data of this product using the rechargeable lithium battery to
supply the electric, therefore, do not let the product with power off for a
long tim e (more than 6 months) to cause the low battery and let the kept
data missing (system parameter, recipe, resume...)
1.1.7. Maintenance Checks
1. Prohibiting touch HMI internal, otherwise it may cause electric shock.
2. Prohibiting dismantle the operation panel when power is on, otherwise, it
may cause electric shock.
3. When the power is off for 3 minutes, should not touch the terminal block,
otherwise, the residual voltage may cause electric shock.
Human-Machine Interface
HM-730S
V1.02
2013-08-05
1
3
1.1.2. Power Wiring
1.
The input power of HMI using a DC power supply, voltage range of 24 ±
20% VDC, too much or too less will be serious damage to HMI. Regularly
check the power supply of DC p ower source to see if it is stable or not.
2.
To avoid electric shock, before connecting to the communications cable or
download cable, please cut off the HMI power.
3.
DC power supply must be properly isolated from the main AC power.
4.
Do not let the input circui t of HMI and inductive load (solenoid or
electromagnetic switch), inverter or driver to share the power supply.
1.1.3.
Power wiring method
1.
Please remove the quick connector from HMI body when wiring.
2.
Only one cable can be inserted into the cable socket of quick connector.
3.
24VDC' anode connect to the terminal marked as a "+", and 24VDC
cathode connect to the terminal marked as a "-".
4.
When error compulsorily pulls out the wire, you should re -check the
connection cable and start.
5.
The proposed wiring material are as follows:
Type
Wire Gauge (AW G)
Multi-core wire
22~16
Single-core wire
22~16
1.1.4. FG grounding requirements
1.
Please use at least 2mm 2(AWG14) as a grounding conductor, grounding
impedance must be less than 100Ω (class3).
2.
Please use the independent grounding pole, should not connect to the
grounding conductor of power circuit.
3.
Ground conductors should be as short and as large in size as possible.
The conductors must always be large enough to carry the maximum short
circuit current of the path being considered. Ground conductors should be
connected to a tree from a central star earth ground point. This ensures
that no ground conductor carries current from any other branch.
4.
The vent of HMI should not obstructed, otherwise, it may easily cause a
malfunction.
1.2. Installation and storage environmental conditions
The product must be kept in the shipping carton before installation. In order to
retain the warranty coverage, the HMI should be stored properly when it is not
to be used for an extended period of time. Some storage suggestions are: :
1.
The storage location should be dry with no dust, should've better with
correctly packaged and placed on a solid shelf surface.
2.
Store within an ambient temperature range of -20°C~+60°C (-4°F~140°F).
3.
Storage location' ambient relative humidity must be within the range of
10% to 90% without condensation
4.
Do not store in the environment of corrosive gases and liquids .
5.
The suitable installation environm ent : No heat-radiating elements, no
water droplets, no vapor, no dust and oily dust' place; non -corrosive,
flammable gases, liquids spaces; no airborne dust or metallic particles of
places; sturdy no vibration、no electromagnetic noise interference' places.
2. Serial port pin definitions
COM1 – ( Support RS232 / RS485 )
Pin
1
RS485+
2
RS232 RXD
3
RS232 TXD
4
Terminal resistor for RS485+
5
Signal Ground
6
RS485-
7
RS232 RTS
D type / 9P
8
RS232 CTS
Female socket
9
+5VDC Output ( Maximum 100mA )
Stripped Length
Torque
7~8 mm
4.5 lb-inch
7~8 mm
4.5 lb-inch
2
.
Pin Definitions