INTENDED USE OF PRODUCT

The Single Station Remote Alarm is used to monitor and report the status of inlet pressure on Switchover Systems
and Autoswitch Systems. The Alarm can be configured to operate with either normally open or normally closed
pressure switch contacts. The Alarm contains a set of relay contacts that can be used to control any device that
can be activated using a normally open or normally closed switch. One example of such a device would be the
CONCOA telephone dialer (PN 5295306).
Connections to the Alarm are made through input and output connectors. Customer supplied cables are easily
soldered to the connectors prior to plugging the connectors into the Alarm. For connector pin assignments
please refer to the "CONNECTING THE ALARM" section of this manual.

USER RESPONSIBILITY

Service to this product should only be performed by CONCOA or an authorized CONCOA agent. Requests for
service may be made through CONCOA CUSTOMER SERVICE at 1-800-225-0473. Written requests may
be made using CONCOA's FAX number at 1-757-422-3125 or CONCOA's E-MAIL at [email protected].
CONCOA accepts no responsibility for damage or injury if this product is modified in any way.
CONCOA assumes/accepts no liability or responsibility for damage to individuals or equipment that may occur
when using this product.
GENERAL SAFETY PRACTICES
Basic safety precautions must be followed to reduce the risk of fire, electrical shock or injury.
a. Connect the Alarm to the correct line voltage. The product is supplied with either a 120 VAC or
220VAC wall mount power supply.
b. While the Alarm is dust and moisture resistant, it should be installed in a location where it will not
be subjected to rain or high concentrations of dust. Never pour or spray liquids directly onto the
product.
c. Install the Alarm where the ambient temperature range while operating is between 0°F and 140°F.
d. Do not install the product in hazardous locations.
e. If product appears damaged in any way, do not use and request service from CONCOA.
f.
Do not attempt to operate the Alarm with the cover off.

CONNECTING THE ALARM

To connect the Single Station Remote Alarm to a Switchover or Autoswitch system, an interface cable must
be made. The Autoswitch/Switchover systems are shipped with a connector that is used for this cable. Two
connectors are provided with the alarm. One is used to connect to the Autoswitch/Switchover and the other is
to connect to the output relay contacts.
To perform the assembly task you will need a soldering station or pencil, rosin core solder, and a wire stripper.
It would also be helpful to have a vise to hold a connector while soldering the wires to it.
OPTION 1: For Switchover Systems that have a 4 pin circular connector.
It will be necessary to obtain a 4 conductor cable. The length of the cable is determined by the application
but should be limited to no longer than 1500 feet. It is recommended that 22 AWG stranded wire be
used. (Alpha #5004C or Belden #8444 are acceptable types.)