[Equipment Parameters and Their Settings]
Equipment
Variable
parameter
Light receiving level setting for detection
【01.】
0-4095
Threshold
judgment
(0-100%)
Setting of a change in light receiving quantity
【02.】
0-4095
Hysteresis
(0-100%)
required to turn the detection status from ON to OFF
【03.】
0-4095
Light receiving level alarm upper limit
Alarm Hi
(0-100%)
setting
【04.】
0-4095
Light receiving level alarm lower limit
Alarm Lo
(0-100%)
setting
【05.】
3-255
Light receiving level alarm monitoring time
Alarm
setting (1 = 100ms)
monitoring time
【06.】
Through-beam type, Dark (interrupt) ON
0
Light ON/Dark
1
Through-beam type, Light (transmit) ON
ON
2
Reflection type, Dark (no reflection) ON
3
Reflection type, Light (reflection) ON
Simplified mode (Preventive maintenance
【07.】
0
Operation
function disabled)
mode
Normal mode (Preventive maintenance
1
function enabled)
【08.】
AD value indication (0-4095 Digit)
0
Light receiving
1
0-100% indication
level indication
【09.】
High
0
Light emitting
1
Middle
power
Low
2
【10.】
ON delay time setting (1=100ms)
0-999
ON Delay
OFF delay time setting (1=100ms)
【11.】
0-999
OFF Delay
One-shot time setting (1=100ms)
【12.】
0-999
One Shot
【17.】
0
Automatic setting disabled
Automatic
1
Only automatic address setting enabled
address/parameter
setting
Only automatic parameter setting enabled
(for master unit
2
*
Linked with the parameters of the master
only)
unit
3
Automatic address and parameter setting
【18.】
0
Normal indication
7-segment display
orientation change
1
180˚ inverted indication
(for master unit
only)
Factory-set
Description
variable
50
5
0
0
50
0
0
0
0
0
0
0
0
0
-L*F1011 10/11-
[Specifications]
■General speci cations
Operating ambient temperature/humidity
Storing ambient temperature/humidity
Vibration resistance
Shock resistance
Operating atmosphere
Operating altitude
*2
Pollution level
*3
*
1 When 1 or 2 slave units are connected: 0 to 55°C
When 3 to 10 slave units are connected: 0 to 50°C
When 11 or more slave units are connected: 0 to 45°C
*
2 Do not use or store AnyWireASLINK devices in an environment where the pressure
exceeds the atmospheric pressure at an altitude of 0 meters. Doing so may result in
malfunction.
*
3 "Pollution level" is an index that indicates the degree of occurrence of conductive
substances in the environment where the device is used.
Pollution level 2 means the occurrence of only pollution by non-conductive substances.
In such an environment, however, electrical conduction could occur due to accidental
condensation.
■Transmission speci cations
Service power supply
24V DC +15% to -10% (21.6 to 27.6V DC)
voltage
with a ripple of 0.5Vp-p or less
DC power supply superimposed total
Transmission method
frame/cyclic method
Frame/bit synchronization method
Synchronization method
Transmission procedure
AnyWireASLINK protocol
Connection mode
Bus type (Multi-drop method, T-branch
method, Tree branch method)
Number of connection
512 max. (IN: 256, OUT: 256)
points
Up to 128 units
Number of connection
units
RAS function
Detection of transmission line disconnection,
transmission line short-circuit, transmission
power supply drop, and
duplicated/unregistered ID
■Individual speci cations
Number of occupied points
Response time
*4
Current consumption
Weight
Protection rating
Operating ambient
illuminance
*
4 A time required for ON/OFF detection until transmission signal output.
To update data, 1-cycle transmission time is required in addition to the response time.
[Detecting Distance]
■Fiber unit
Model
AFT-4
AFT-1
AFT-2
AFT-1-1
*
5 For 0-100% light receiving level indication setting
*
6 For ON/OFF setting
0 – 55°C
*1
, 10 – 90%RH No condensation
-25 – 75°C, 10 – 90%RH No condensation
Based on JIS B 3502 and IEC 61131-2
Based on JIS B 3502 and IEC 61131-2
No corrosive gas
0 – 2000m
2 or less
Input 1 point
1 or 2 cycles
24V-0V
25mA
DP-DN
1.9mA
22g (Master unit)
17g (Slave unit)
IP40
Incandescent lamp
3000lx or less
Sunlight
10000lx or less
Detecting distance (mm)
Diagnosis
Diagnosis
enabled *
disabled *
5
410
160
300
170
6
600
210
420
240