3onedata GW11X8-8D (3IN1)-RJ45 Series Benutzerhandbuch - Seite 4
Blättern Sie online oder laden Sie pdf Benutzerhandbuch für Gateway 3onedata GW11X8-8D (3IN1)-RJ45 Series herunter. 3onedata GW11X8-8D (3IN1)-RJ45 Series 4 Seiten. Modbus gateway
about 2 mm to allow room for sliding the Modbus gateway
between the wall and the screws.
5. Before tightening the screws into the wall, make sure the
screw head and shaft size are suitable by inserting the
screw through one of the keyhole-shaped apertures of
the gateway.
6. Once the screws are fixed in the wall, hang the Modbus
gateway on the 2 screws through the large opening of the
keyhole-shaped apertures, and then slide the switch
downwards. Tighten the two screws for added stability, as
shown below.
Wiring Requirements
Cable laying need to meet the following requirements,
1. It is needed to check whether the type, quantity and
specification of cable match the requirement before
cable laying;
2. It is needed to check the cable is damaged or not, factory
records and quality assurance booklet before cable
laying;
3. The required cable specification, quantity, direction and
laying position need to match construction requirements,
and cable length depends on actual position;
4. All the cable cannot have break-down and terminal in the
middle;
5. Cables should be straight in the hallways and turning;
6. Cable should be straight in the groove, and cannot
beyond the groove in case of holding back the inlet and
outlet holes. Cables should be banded and fixed when
they are out of the groove;
7. User cable should be separated from the power lines.
Cables, power lines and grounding lines cannot be
overlapped and mixed when they are in the same groove
road. When cable is too long, it cannot hold down other
cable, but structure in the middle of alignment rack;
8. Pigtail cannot be tied and swerved as less as possible.
Swerving radius cannot be too small (small swerving
causes terrible loss of link). Its banding should be
moderate, not too tight, and should be separated from
other cables;
9. It should have corresponding simple signal at both sides
of the cable for maintaining.
【Specification】
Ethernet port
Standard: 10Base-T, 100Base-TX
Protocol: Support Modbus TCP, Modbus RTU, Modbus
ASCII, IP, APR, ICMP, DNS and DHCP
Signal: Rx+, Rx-, Tx+, Tx-
Speed: 10/100Mbps
Working: Full duplex and half duplex
Transfer distance: 100m
Connector: RJ45
Serial port
Serial port number: RS-232/485/422
RS-232 signal: DSR, RTS, GND, TXD, RXD, DCD, CTS,
DTR
RS-485 signal: D+, D-, GND
RS-422 signal: T+, T-, R+, R-, GND
Parity bit: None, Even, Odd, Space, Mark
Data bit: 7bit, 8bit
Stop bit: 1bit, 2bit
Baud rate: 300bps~115200bps
RS-232 transfer distance: 15m
RS-485/422 transfer distance: 1200m
Direction control: RS-485 using data flow automatic control
technology
Load capacity: support 32 point polling environment
(customizable 128 points)
Connector: RJ45
LED Indicator
Run indicator: RUN
- 4 -
Power supply indicator: PWR
Ethernet Link/Act indicator: LINK
RS-232/485/422 port transmit data indicator: TX
RS-232/485/422 port receive data indicator: RX
Power requirements
Input voltage: 12~48VDC
Type of input: 3-pin 5.08mm spacing terminal block
No-load consumption: 1.8W@12VDC
Full-load consumption: 3.9W@12VDC
Environment limits
Working temperature: -40~85°C
Storage temperature: -40~85°C
Relative humidity: 5%~95%(non-condensing)
Mechanical
Shell: IP30 protection, metal shell
Installation: Wall mounting
Weight: 580g
Size (L×W×H): 170.0mm×110.0mm×31.5mm
Standard
EMI: FCC Part 15, CISPR (EN55022) class A
EMS:
IEC 61000-4-2 (ESD), Level 4
Contact: 8 kV
Air: 15 kV
IEC 61000-4-4 (EFT), Level 3
Power: 2 kV
Signal: 1 kV
IEC 61000-4-5 (Surge), Level 3
Power: common mode
2 kV
difference mode 1 kV
Signal: common mode
1 kV
difference mode 1 kV
Shock: IEC 60068-2-27
Free fall: IEC 60068-2-32
Vibration: IEC 60068-2-6
Warranty: 3 years
Certificates
CE, FCC, RoHS, UL508 (pending)