Duke RUF 48 Service-Handbuch - Seite 4

Blättern Sie online oder laden Sie pdf Service-Handbuch für Kühlschrank Duke RUF 48 herunter. Duke RUF 48 12 Seiten. Refrigerated counter
Auch für Duke RUF 48: Installations- und Betriebshandbuch (8 seiten)

Service Manual for Refrigerated Back Bar Model RUF 48

SPECIFICATIONS

MODEL DESCRIPTION
RUF 48 48" Refrigerated
Back Bar
MODEL
DESCRIPTION
RUF 48
48" Refrigerated 36.00 In.
Back Bar

INSTALLATION

Location

The unit represented in this manual is intended
for indoor use only. Be sure the chosen location
has a floor or counter strong enough to support
the total weight of the unit. Reinforce the floor
or counter if necessary to provide for maximum
loading. For the most efficient operation, be sure
to provide good air circulation inside and out.
The outline dimensional drawing for the unit is
shown below in Figures 1.
Figure 1
48" Refrigerated Back Bar (RUF 48)

Inside Unit

Provide adequate space along the front, back and
sides taking care to not block airflow to the fans.
4
VOLTAGE
AMPS Ph.
120 VAC (60 Hz)
6.4
220 VAC (50 Hz)
3.2
hEIGhT
WIDTh
LENGTh
29.50 In.
48.00 In.

Outside Unit

Be sure that the unit has access to ample air;
1
avoid hot corners and locations near stoves and
1
ovens.

Leveling

Be sure that the unit is placed on a firm, flat
surface/floor. Check for cracks in flooring or tile
and avoid these areas if possible. If necessary
place support pads, properly rated for the weight
of the unit, to "bridge" uneven or cracked flooring.
Level unit accordingly.

Stabilizing

Use the leg adjustments to insure that the unit is
solid to the floor surface at all four contact points.
Insure that the unit does not "rock" when pressure
is applied to the top corners.

Electrical Connection

The RUF 48 is available as a 120VAC, 60 Hz or
as a 220VAC, 50 Hz dependent on model. All
electrical connections should be performed by a
certified electrician and should comply with local
electrical codes for your municipality.
REFER TO ThE AMPERAGE DATA
LIST IN ThE SPECIFICATIONS OR
ThE SERIAL TAG DATA AND YOUR
LOCAL CODE OR ThE NATIONAL
ELECTRICAL CODE TO BE SURE UNIT
IS CONNECTED TO ThE PROPER
POWER SOURCE.
CIRCUIT OF ThE CORRECT VOLTAGE
AND AMPERAGE MUST BE RUN FOR
CONNECTION OF ThE SUPPLY CORD
OR PERMANENT CONNECTION TO ThE
UNIT. ThE POWER MUST BE TURNED
OFF AND DISCONNECTED WhENEVER
PERFORMING MAINTENANCE OR RE-
PAIR FUNCTIONS.
WARNING
A PROTECTED