Installation Guide | VLT® PROFIBUS DP MCA 101

3 Technical Data

3.1 Cabling Requirements

Terminate the nodes at the physical ends of each segment. If the bus segment is branched, the device furthest from the segment
connector represents the end of the segment.
Terminals 66 and 67 provide a 5 V DC supply, available for external termination.
The PROFIBUS D-sub 9 adapter also features a termination switch. When the D-sub 9 adapter is used, set the termination switch
on the fieldbus option to OFF to avoid double termination.
When the fieldbus is extended with a repeater, terminate the extension at both ends.
To avoid impedance mismatch, use the same cable type throughout the entire network.

3.2 Cable Specifications

Table 2: Cable Specifications
Impedance at a measuring frequency from 3–20 MHz
Resistance
Capacitance
Damping (total wire length)
Cross-section
Cable type
Shielding
Danfoss A/S © 2019.03
N O T I C E
N O T I C E
N O T I C E
135–165 Ω
<110 Ω/km
<30 pF/m
Maximum 9 dB over the whole wire length.
2
Maximum 0.34 mm
, AWG 22.
Twisted in pairs, 1 x 2, 2 x 2, or 1 x 4 wires.
Copper-braided shield, or braided shield and foil shield.
Technical Data