D. Installation Guidelines
1. Install the ESP air cleaner as close as possible to the kitchen exhaust hood.
2. Install the ESP unit on either side of the kitchen hood. See figure 1. This is the best position to
maintain and clean the unit.
3. The ESP unit should be installed in a position with easy access for cleaning purposes. See
maintenance space requirements on specification sheets.
4. If the ESP unit cannot be installed next to the exhaust hood, connect the unit with a straight duct
of a minimum of one metre on the inlet and outlet side, or if using a bend make sure it is fitted with
veins. See figure 2. This will balance the air within the ESP unit.
5. The ESP unit can be set up for the airflow from right to left or left to right. When ordering the unit,
specify the airflow direction.
6. The airflow volume and air velocity through the ESP unit should be below the rated
volume/velocity.
7. The ESP unit should be installed in a horizontal position.
8. The ESP unit should be automatically powered when the exhaust fan is running.