Danfoss ECtemp 610 Installationshandbuch - Seite 10

Blättern Sie online oder laden Sie pdf Installationshandbuch für Thermostat Danfoss ECtemp 610 herunter. Danfoss ECtemp 610 16 Seiten. Electronic thermostat ip44

Danfoss ECtemp 610 Installationshandbuch
6.
Install sensor using the supplied sensor cable -
NTC 15 kΩ @ 25 °C.
Press out the blanket located at the bottom of the
thermostat and insert the seal nipple.
Connect sensor to terminals 6+7.
The sensor cable can be extended up to 50 m with
1,5 mm² installation cable without affecting the ac-
curacy of the thermostat.
Do not place the cable parallel to other installation
cables as undesirable signals may be induced.
The installation must be permanent.
If the sensor is to be built in, used for pipe applica-
tions, or exposed to pressure, always install it in a
conduit.
7.
Turn on the power supply.
10
ECtemp 610
Installation Guide