Danfoss KP 61 Installationshandbuch - Seite 3

Blättern Sie online oder laden Sie pdf Installationshandbuch für Thermostat Danfoss KP 61 herunter. Danfoss KP 61 4 Seiten. Vapour charge, adsorption charge (cross ambient)
Auch für Danfoss KP 61: Installationshandbuch (2 seiten), Anweisungen (4 seiten)

Danfoss KP 61 Installationshandbuch
Adjustment spindles location
Note
Remove lockplate before thermostat
adjustment. Replace lockplate after
adjustment (if desired).
RANGE
See printed instruction on top of control
increase temp. (warmer): turn CW
decrease temp. (colder): turn CCW
(use adjustment knob)
Determination of differential
For KP w/ vapor charge and auto. reset (KP 61, KP 62, KP 63, KP 68, KP 69): Use graphs to determine correct differential.
Example:
HSP = 5.6 °C (45 °F) =>
LSP = 0 °C (32 °F)
© Danfoss A/S (AC-MCI / jmn), 2013-11
DIFF (from graph):
7.2 °C (13 °F) (value which has to be
set on diff. scale).
DKRCC.PI.CA0.C1.22 / 520H8304
DIFFERENTIAL
See printed instruction on top of control
(use adjustment knob or screwdriver)
For KP w/ adsorption charge (KP 71, KP 73, KP 75, KP 77, KP 79, KP 81):
The differential will be HSP less LSP
Example:
HSP – LSP = DIFF.
7 °C – 5 °C = 2 °C
(45 °F)(35 °F) (10 °F)
Note:
(Load Option A)
(Load Option B)
CUT-IN
= HSP or
CUT-IN
CUT-OUT = LSP
CUT-OUT = HSP
See "Wiring"
Increase: turn CW
decrease: turn CCW
= LSP