Analog input selection
Configure Analog signal type by selecting DIP switch as shown in below table (green denotes ON).
Analog Input
0 - 10 V (Default)
0 - 5 V
4 - 20 mA
0 - 20 mA
Analog input sharing
Configure analog input to be shared if needed as below (green denotes ON).
Stepper driver 1
Analog Input AI1
Analog input AI2
Stepper driver 2
Analog Input AI1
Analog input AI2
Digital output signal
One digital output is present in EKF and only alarm activates the output.
Output type
Load type
Maximum allowed current
Maximum Voltage
Stepper Motor Output
• The stepper motor is connected to the "Stepper Valve" terminals (see connection overview) with a standard M12
connection cable or JST XHP-5 connector.
• The default valve setting in EKF 1A/2A is: No Valve.
• The correct valve must be defined as per section DIP Switch – Valve
Valve Cable Connection
Danfoss recommends to use ETS 5M and ETS 6 valves to be connected to JST XHP-5 pin connectors instead of 4 pole terminal
block, but it is possible to connect to terminal block, follow color codes of wires of coil as shown in table below.
Stepper valve
A1
A2
B1
B2
While using JST 5pin, its plug and play for ETS 6 and ETS 5M valves.
Guideline for long M12 cables for Danfoss stepper motor valves
• Long cables will lead to degradation of performance.
• Cable length for stepper motor connection must be less than 30 m.
• Danfoss recommends to use 4-20 mA signal for long distances and use shorter cable between driver and valve.
6 | AN375548103097en-000202
1
2
1
2
1
2
Similar to NPN, open collector
Resistive only
10 mA
28 V (allow 24 V DC + 15%)
ETS/KVS/CCM/ CCMT/CTR/ CCMT L
White
Black
Red
Green
DIP Switch
3
4
5
6
DIP Switch
3
4
5
6
DIP Switch
3
4
5
6
ETS 5M
Brown
Black
Orange
Yellow
7
8
7
8
7
8
ETS 6
Orange
Yellow
Red
Black