Dungs MPA 4112 V2.0 Benutzerhandbuch - Seite 16
Blättern Sie online oder laden Sie pdf Benutzerhandbuch für Brenner Dungs MPA 4112 V2.0 herunter. Dungs MPA 4112 V2.0 16 Seiten. Automatic burner control system
Auch für Dungs MPA 4112 V2.0: Benutzerhandbuch (16 seiten)
Safety-relevant components
J
Valve proving systems
Gas pressure sensing device
Air pressure sensing device o
Gas failure switch
Automatic burner control system
UV flame sensor
1
Gas pressure regulators
1
Gas valve with valve proving system
2
Gas valve without valve proving system
2
Gas / air ratio control systems
Decreasing performance on account of ageing
1
Gas families II, III
2
Operating hours
3
N / A
not applicable
Lagerzeiten ≤ 1 Jahr verkürzen nicht die konstruktionsbedingte Lebensdauer / Storage time ≤ 1 year does not reduce the designed lifetime /
DUNGS recommends a maximum storage period of 3 years
The Pressure Equipment Directive (PED) and the Directive on the energy performance
of buildings (EPBD) require a regular inspection of heat generators to guarantee a high
degree of long-term efficiency and thus minimal environmental impact.
There is a need to replace safety-related components after they reach the end of
their useful life:
Design-related service life
Cycle number
Years
250 000
50 000
250 000
N / A
250 000
N / A
N / A
after error detected
DN ≤ 25
200 000
25 < DN ≤ 80 100 000
80 < DN ≤ 150 50 000
N / A
Storage periods
Standard
10
EN 1643
10
EN 1854
10
EN 1854
10
EN 1854
EN 298
10
EN 230
10 000 h³
---
EN 88-1
15
EN 88-2
EN 1643
10
EN 161
EN 88-1
10
EN 12067-2
Karl Dungs GmbH & Co. KG
Karl-Dungs-Platz 1
D-73660 Urbach, Germany
Telephone +49 7181-804-0
Fax
www.dungs.com
Permanent storage temperature
0...45 °C
32...113 °F
+49 7181-804-166
16 ... 16