Belimo UK24BAC Handbuch Technische Daten - Seite 11
Blättern Sie online oder laden Sie pdf Handbuch Technische Daten für Gateway Belimo UK24BAC herunter. Belimo UK24BAC 20 Seiten. Belimo gateway mp to bacnet ms/tp
UK24BAC
Protocol Implementation Conformance Statement - PICS
General information
Standard objects (general)
www.belimo.com
Belimo Gateway MP to BACnet MS/TP
Date:
Vendor Name:
Vendor ID:
Product Name:
Product Model Number:
Applications Software Version:
Firmware Revision:
BACnet Protocol Revision:
Product Description:
The UK24BAC device is a gateway from MP to BACnet MS/TP. Up to eight MP-bus-capable
Belimo actuators can be connected on the MP-Bus side. This permits the actuator functions as
well as the connected sensors to be integrated directly into BACnet.
The datapoint mapping from MP to BACnet is fix defined. The configuration of the device is
accomplished with DIP switches and with Standard BACnet clients.
BACnet Standard Device Profile:
BACnet Interoperability Building Blocks supported:
Data Sharing - ReadProperty-B (DS-RP-B)
Data Sharing - ReadPropertyMultiple-B (DS-RPM-B)
Data Sharing - WriteProperty-B (DS-WP-B)
Data Sharing - WritePropertyMultiple-B (DS-WPM-B)
Data Sharing - COV-Unsolicited-B (DS-COVU-B)
Device Management - DynamicDeviceBinding-B (DM-DDB-B)
Device Management - DynamicObjectBinding-B (DM-DOB-B)
Device Management - DeviceCommunicationControl-B (DM-DCC-B)
Segmentation Capability:
Data Link Layer Options:
Device Address Binding:
Networking Options:
Character Sets Supported: ANSI X3.4 / UTF-8
These BACnet objects exist only once per device:
Datapoint
-- Device
-- Device ID Offset
-- COV Mode
The Device Object Identifier (Device-ID) is defined by the BACnet MAC address (TS) and
the Device ID Offset: Device-ID=TS+Offset.
The Device Object Name is defined by the Product Name and the Device-ID:
e.g. "UK24BAC_1001"
The calculated value can be overwritten using WriteProperty services. Reset to
automatically calculation by writing an empty object name (empty or space character only).
T9-UK24BAC • en • v1.9 • 06.2018 • Subject to changes
3. February 2014
BELIMO Automation AG
423
UK24BAC
N/A
1.10
1.10
1.10
BACnet Application Specific Controller (B-ASC)
No
MS/TP master,
baud rates: 9'600, 19'200, 38'400, 76'800
No static device binding supported
None
BACnet Object
Device [x]
AV
[1]
MV
[1]
11 / 20